CG i
GAS-FIRED wATER BOILER- sERIEs a -
Boiler Manual
ld
Prepare boiler location - air contamination
Please review the
followi
ng i
nformation
on
potential
combustion air
contamination
problems.
Refer to
Table 1
for products
an
d areas which may cause
contaminated combustion air.
I&
WARNING!
To
prevent
potential of severe personal injury or death,
check for
products
or
areas listed
below before i nstalling boiler. If any of these contaminants are found:
remove contami
nants
permanently
-OR
-
i
solate
boiler and
provide outside
combustion
air. See national,
provinci al or
local
codes
for further
i
nformati on.
Table
1
Corrosive or destructive contaminants and likely locations
Products
t
o avoid
Areas likely
t
o have
contaminant
s
Spray
cans containing
chi
oro/fluorocarbons
Dry cleaning/laundry areas and establishments
Permanent wave solutions
Swimming pools
Chlorinated waxes/cleaners
Metal
fabrication
plants
Chlorine-based swimming pool chemicals
Beauty
shop
s
Calcium chloride used for thawing
Refrigeration
repair shops
Sodium chloride used for water softening
Photo processing plants
Refrigerant
leaks
Auto body shops
Paint or varnish removers
Plastic manufacturing plants
Hydrochloric acid/muriatic acid
Fum~ure
refinishing areas and establishments
Cements
and
glues
New building construction
Antlstatlc fabric softeners used In clothes dryers
Remodeling areas
Chlorine-type bleaches, detergents, and cleaning
Garages wHh
workshop
s
solvents
found
In household laundry rooms
Adhesives used to
fasten
building products and
Buildings under construction (where air Is
other similar products
contsmlnated with particulates)
Airborne particulates
(drywall
dust,
fiberglass
particles, road or
gravel
dust, lint, etc.)
I&
W ARNING
I
CONSTRUCTION DUST HAZARD
-
Airborne particulates, such as drywall
dust
or
fiberglass
dust,
will
cau
se blockage of the
CGi
burners, resulting
in carbon mon
oxide
production,
a fire hazard,
or
building freeze dan1age.
If
the
boiler is operated
during
construction,
you
must
isolate
the
boiler
to provide
dean
air
for
combustion.
If you are
unable to ensure uncontaminated
air
In the boiler vlclnHy at all Urnes, you muslin-
spect the
boiler
at least once
weekly. When
inspect
i ng, clean the burners if necessary
using the procedure
given
on page 45. Failure to follow these guidelines could result
in
severe personal injury, death or
substant ial
property
dam
age.