Weil-McLain CGi Series 3 Installation And Maintenance Manual page 30

Gas-fired
Hide thumbs Also See for CGi Series 3:
Table of Contents

Advertisement

CG i
GAS-FIRED
wATER BOILER-
sERIEs a -
Boiler Manual
5
Gas piping
Connecting gas supply piping
to
boiler
I.
Remove
jacket front
panel
and
refer
to
Figure 26
to
pipe
gas
to
boiler.
a.
Install
drip
leg
at
inlet
of gas connection
to
boiler.
Where
local
utility
re<Juires
drip
leg
to be extended
to
the
floor,
use appropnate length of
pipe
between
cap
and
tee.
b.
Install
ground
joint union
for
servicing,
when
re-
q uired.
c.
Install
manual
shutoff
valve in
gas supply
piping
out-
side boiler jacket when
required
by
local
codes
or
utility
requirements.
d.
In
Canada
-
When
using
manual
main shutoff valve, it
must
be
identified
by
the installer.
2.
Support
piping
with
hangers,
not by
boiler or
its
accessories.
3.
Purge
all
air
from
gas
supply piping.
4.
Before
placing boiler
in
operation,
check
boiler
and
its
gas
connection
for
leaks.
a.
Close
manual main
shutoff
valve during
any pressure
testing
at
less
than
13"
w.c.
b.
Disconnect boiler
and gas
valve
from
gas
supply
piping
during
any pressure
testing greater than
13" w.c.
'" 1&-,-,
W
.,.,.,
AR
,.,.
N
""
IN~GI
Do not check
for
gas
leaks with
an
open
flame
-
use
bubble
test
Failure
to
use bubble
test
or check fo
r
gas
leaks
can cause severe
personal
injury,
death
or
substantial
property
dan1age.
5.
Use
pipe dope
compatible
with
propane gases.
Apply
sparingly only
to
male threads of pipe joints
so
that
pipe dope
does no
t block gas
flow.
I&
WARNING!
Failure
to
apply
pipe
dope
as detailed above
can
result in
severe
personal
injury,
death or
Natural Gas:
I.
Refer
to
Table 7
for
pipe
length
and diameter. Base on
rated
boiler input {divide
by
1,000
to
obtain cubic feet per hour).
Table 7
is o nly
for
gas
with specific gravity
0.60,
with
a
pressure drop through
the gas piping of 0.30"
w.c.
For
additional
gas
pipe sizing
infom1ation,
refer to
ANSI
Z223.
1
(or
BI49.I or
BI49.2 fo
r Canadian
installations).
2.
Inlet pressure
required
at
gas
valve inlet:
tvtaximum:
13"
w.c.
tvtinirnum:
5"
w.c.
JV!anifold
gas pressure: 3.5" w.c.
3.
Install
100%
lockup
gas pressure regulator
in
su
pply line
if
inlet
pressure
exceeds
13"
w.c.
Adjust for
I
3"
w.c.
maxi-
mum.
Propane Gas:
I.
Contact
gas
supplier
to
size
pipes,
tanks and
I
00%
lockup
gas
pressure regulator.
2. Adjust propane supply
regulator
provided by gas
supplier
for
13"
w.c.
maximmn
pressure.
3.
Inlet pressure
required at
gas
valve inlet:
Maximum:
1
3"
w.c.
tvtinirnum:
11
,
w.c.
Manifold
gas
pressure:
10"
w.c.
substantial property
dam
age.
Figure 26
Gas
supply piping
Table 7
Pipe capacity
for
0.60 specific
grav~y
natural
gas
Gas pipe
Capacity of pipe for pipe size of:
length
(Capacity in
cubic
feet
gas
per hour)
(feet)
1/a"
1"
1f/•"
11/a"
10
132
278
520
1050
1800
20
92
190
350
730
1100
30
73
152
285
590
880
40
83
130
245
500
760
50
58
115
215
440
670
75
45
93
175
360
545
100
38
79
150
305
460
150
31
64
120
250
360
71028