Troubleshooting - procedure
!&WARNING!
Label all
wires
prior
to dis-
connection
when servicing
controls. Wiring errors
can
cause
improper
and danger-
ous operation.
Check the following:
I. Wire connectors to
control
module are securely
plugged in at
module
and
originating
control.
2.
Air
pressure S\vitch hoses are properly
and
securely plugged
in and
are
not
damaged.
!&WARNING!
Never jmnper
(bypass)
roll-
out
thermal
fuse
element
or
any
other
device
except
fo
r
momentary testing as
outlined in
Troubleshoot-
Ing
Charts. Severe
personal
injury,
death
or substantial
property damage
can
result.
3.
Gas
pressures:
a.
With
boiler
off
-
13" w.c.
maximum natural or
propane
gas
pres-
sure
upstream
of gas valve.
b. With boiler on:
s•
w.c.
minimum natural gas
pressure
or
11" w.c. propane gas
pressure
upstream
of gas valve.
3
in"
w.c.
minimum natural gas
pressure
or
10" w.c. propane gas
pressure downstream of gas valve-
Can
be
adjusted
by regula-
tor
on gas valve.
4.
Verify gas
manifold
pressure
(downstream
of
gas
valve):
Before troubleshooting:
a. Natural gas:
Manifold pressure,high
tire: 3.50"w.c.
1.
Have the
following
items:
a.
Voltmeter that
can
check
120 V AC
and 24
VAC.
CGi-4
only- Manifold pressure, low
tire: 090" w.c.
while
in
low fire at
start·up (60seconds)
b. Propane
gas:
Manifold pressure,high
tire: IO.O"w.c.
b.
Microammeter
with
a minimum
scale range of 0-25.
CGi-4
only- Manifold pressure, low
tire: 3SO" w.c.
while
in
low fire at
start·up (60 seconds)
c. Continuity checker.
d U-tube manometer.
c. If necessary, adjust gas pressure
on
the
gas
valve as
shown
below. After
adjustments,
refer
to
page 35
to
check the flame.
2.
Check for 120
VAC
(minimum
102 VAC
to
maximmn
132 V AC) to boiler.
3.
Make
sure
them1ostat
is
calling
for heat
and
contacts (including appropriate zone
controls) are closed.
Check for 24
VAC
between them1ostat wire nuts and ground.
pressure a4ustment
lloueywel
two-otage
gas
vtlve
11b
Troubleshooting - components
Air pressure switch
NOTICE
NOTICE
50
Make
sure
boiler water temperature is
I
00
°F
or cooler
before starting procedure to
obtain
appropriate readings.
The
boiler
will
not
operate
correctly unless
pressure S\vitch hoses are correctly
located.
The
red
hose connects from the right side
(negative) hose
barb
to the flue collector. The
white hose connects
from
the
left
side
(posi-
tive) hose
barb
of the
switch
to
the
connector
box
(between
flue
collector and
inducer) as
shown
in Figure
36,
page
49.
Chec
k pressure switch setting
1.
See
Figure 36,
page 49,
and Table 9.
2. Remove
both
air pressure switch hoses from
air
pressure
switch.
3.
Install
tees
and tubing as
shown
in
Figure
38.
page 49, to
indined
manometer.
4.
Turn
off
gas
valve
and
set
thermostat
to call
for heaL Inducer
will
run
but burners
will not
ignite.
5.
Check
for
24
VAC
between both air pressure switch
terminals.
Part
Number 550-142-780/0712