GAS-FIRED wATER BOILER- sERIEs a -
Boiler Manual
4d
28
Piping - low temperature systems
SYSTEM-bypass piping
method
This
piping method
is
called a
system-bypass
because
part
of
the
circulator
flow
bypasses
the
system
(thro
ugh
valve 7a). This
bypassed
hot water fro
m
the
boiler outlet
mixes
with cooler
system
return
water temperature in
order
to
provide minimum 130°F
return
water to
the
boiler. Valve
7b
will most often be
full
open, but may
need to
be
slightly
dosed
on some low pressure drop
sys-
tems
in
order to
cause
enough
flow thro
ugh
valve 7a.
Figure 24
is an alternative
piping method
that provides
return
water
temperature
control
for
boilers installed
o
n converted gravity systems
(large water content or
steam systems).
Do not
apply
the
piping of
Figure 24
on
radiant
heat-
ing
systems. It provides
no method regulating
the water
temperature provided
to the
system and could
result
in
excessive water temperature
in
the
radiant
tubing.
System-bypass piping as shown
in Figure 24
can
be
used
with either zone valve or
circulator
zoning. When used
with circulator zoning however, the boiler circulator
(
item 3), must
be
piped
as shown.
It
cannot be used
as
o ne of
the
zoning
circulators.
Do
not
apply system-bypass
piping
if
the
reduced
flow
in
the
system
could cause poor heat
distribution.
That
is, system-bypass piping reduces
the flow
in
the
system
and increases the water temperature supplied
to
the
system. This can cause
increased
heat from
radiators
at the beginning of the
system
and
reduced
heat
from
radiators near
the
end of the system.
Va lve adj ustment
I.
Start
with
valve
7a
fully
dosed
and
7b
fully
open.
2. Gradually
open
valve
7a
while dosing valve
7b
until
the
temperature
at gauge
8
reads at least
130°F
at
all
times.
3.
Valve
7a
regulates the amountofboiler supply water
mixed with return
water. Valve
7b
causes
a pressure
drop in
the
system
needed to
balance
flow
through
valve
7a
and the system.
4. The valve adjustment should
be
done
with
the
system
at
the
coldest expected
temperature
(600F
for converted gravity systems or
high
mass
radiant
systems).
I&
WARNING!
Failure to
prevent low return water temperature
to the
boiler
could
cause
corrosion
of the
boiler
sections o
r
burners, resulting
in
severe personal injury,
death
or
substantial
property damage.
Radiant heating
system
piping
should
in
d
ude a means of
regulating the
boller
return
water temperature
and the
system
supply
temperature
(such as
provided by an
InJec-
tion pumping
control).
Boiler return
water
temperature
will
be
adequately
controlled using the
methods
shovm
in
this
manual
provided the
system supply temperature
is
relatively
cons
tent.
DO NOT
apply the
methods of
this manual
if
the
system
is equipped with
an
outdoor
reset control.
Instead,
provtde controls and piping which
can
regulate the boller
re-
turn
water
temperature
at
no less than 130'F
regardless of
system
supply
temperature.
Contact
your
Weil-Mclain
representative
for
suggested
piping and control methods.
Failure
to
prevent cold return water temperature
to
the
boiler
could
cause corrosion
damage
to the
sections o
r
burners,
resulting
in
possible severe
personal
injury,
death
o
r
substantial
property dan1age.
Part
Number 550-142-780/0712

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cgi-25Cgi-5Cgi-4Cgi-6Cgi-8Cgi-7

Table of Contents