Boiler Manual
3e
Venting - direct exhaust - termination
I&
WARNING!
Follow instructions on this
page
when detem1ining vent
location
to
avoid possibility of severe
personal
injury, death or substantial property
damage.
l. Locate
the
boiler and vent penetration
through the
wall so
all
requirements o
n
this page
and
in
Fig-
ure
12 will
be
met. Also
follow
vent
manufacturer's
instructions.
2. Gases
will form
white plume
in
winter. Plume
could
obstruct window view.
3.
Prevailing
winds could cause freezi ng of condensate
and water/ice buildup on vent
termination,
building,
plants or roof.
Ice
buildup on vent terminatio
n
can
cause boiler shutdown and building
freeze up.
4. Winds over 3
1 mph can
cause nuisance boiler
shut-
down
if boiler is sidewall vented. This could
result
in
loss
of
heat
to building, causing freeze
up.
5. Locate or guard vent
termination
to
prevent
con·
densate
from damaging exterior surfaces.
6. Locate the vent termination well
away
from
trees,
shrubs,
and
decorative
items.
7. Locate or guard vent
to prevent accidental
contact
by
people or pets.
8. Do
not
terminate
vent
in
window
well, stairwell,
alcove, courtyard, or other
recessed
areas.
9. Do
not
wrap
or
insulate
vent
pipe or
fittings.
l
0. Do
not
terminate
vent
above
any door
or window.
Condensate
can
fre.
e .ze, causing
ice
formations.
11
.
Do
not
connect
Any
o ther
appliance
to
vent
pipe.
Multiple boilers to a commo
n vent
pipe.
Figure 12
Vent termination
minimum
clearances
Optional
Snorkeling
Part
Number
550-142-780/0712
12.
Canadian installations
-
See
Bl49.
1 or
Bl49.2
Installatio
n
Code. Tem1inate vent no
less
than 6
feet from another combustion
air
inlet, 3
fe.
e t
from
any other building opening,
and
3 feet fro
m
any gas
service regulator.
13.
See
Figure
12, showing
that the
vent must
temli-
nate:
more
than
4
feet
below
or
to
side
of
all
doors
or windows.
more
than
I
foot
above grade
or
anticipated
snow line.
at least
7
feet above public walkway.
3
feet
above
any forced air
intake
within
I
0
feet.
14.
Vent
must
also
terminate:
at least
6 feet away from adjacent walls.
no
closer than 5
feet
below
roof
overhang.
at least
4
feet
horizontally (and
in
no
case
above or below unless
a
4
foot horizontal
distance
is
maintained) from electric meters,
gas meters,
regulators, relief
valves, and
other
equipment.
IS.
Site conditions
may dictate
greater
clearances.
16.
Do
no
t extend
exposed
vent
pipe outside
of
building
more
than
4 feet.
Condensate could freeze
and
block vent pipe.
I&
WARNING!
A
gas vent extending through an
exterior
wall shall
notterminate
ad-
jacent to the wall or below building
extensions such as eaves, parapets,
balconies o
r
decks.
Failure to
com-
ply could
result in
severe personal
injury,
death
or substantial property
dan1age.
17