Weil-McLain CGi Series 3 Installation And Maintenance Manual page 26

Gas-fired
Hide thumbs Also See for CGi Series 3:
Table of Contents

Advertisement

CG i
GAS-FIRED wATER BOILER- sERIEs a -
Boiler Manual
4d
26
Piping - low temperature systems
BOILER-bypass piping
method
This piping method
(Figure
22
or 23)
is
called
a
boiler-
bypass
because
part
of
the
circulator
flow is bypassed
around the
boiler
(through
valve 7a). This method
reduces the flow
rate
throughout
the
boiler, in order
to
raise
the average
water temperature
in
the
boiler enough
to
prevent
flue gas condensation. Boiler-bypass
piping
is
effective
for some boilers
-
including
the CGi
-
provided
the flow rates
are adjusted
according to the
instructions following.
Figures
22
and
23
are
alternative
piping suggestions
for
converted gravity
(large water content or steam
systems) or
radiant heating
system
-
for use
when
primary/secondary piping
can't
be applied
(Figure
24
is another
alternative,
using
system bypass in place of
boiler-bypass
piping. Figure
24
however, is not suitable
for radiant
heating
applications
because
it
does not
protect
the
radiant
system fro
m
possible high water
temperature.)
Boiler-bypass
piping
keeps
system
flow
rate as
high
as
possible and temperature
drop as low
as possible,
help-
ing
to equalize the
building
heat distribution.
Temperature
gauges
Gauge
4a
is optional if the bypass valves
will
be
ad-
justed
using
cold
(or
room temperature) return water
to
the
boiler. (When setting the valves without gauge
4a
installed
-
using
cold
or
room temperature water
-
assmne
the
return
water temperature
to
be
6Q•F.
Set
the valves
so
gauge
8
reads at
least
t
20"F.
Gauge
4b
is
optional on
converted
gravity systems,
but
required
on
radiant
heating
systems
-
to
display
the water temperature
being
supplied
to the
radiant
tubing.
Gauge
8
is
required
on all systems
to
assure reliable
adjustment of the
bypass
valves. The
boiler-mounted
temperature/pressure gauge
can
be
used if a separate
temperature gauge is not installed
Valve adjustment
t
.
Start with
valve
7a
fully dosed
and
7b
fully
open.
2. Gradually open
valve
7a
while
dosing
valve
7b
until
the
temperature
at gauge
8
reads
60 °F
higher
than gauge
48. A
minimum
60°F temperature
rise
through
the
boiler assures a low
enough
flow rate
and high
enough
average
temperature
to prevent
condensation
even with
low
system
return
water
temperature.
3.
Valve
7a
regulates
the
system
flow rate, wllile valve
7b
regulates the boiler
flow rate.
4.
The
boiler-
mounted temperature/pressure gauge
may be used
in
place of a separate gauge
8.
I&
WARNING!
Failure
to
prevent low return water temperature
to
the
boiler
could cause corrosion
of
the
boiler
sections
or
burners,
resulting
in
severe
personal
injury,
death or
substantial
property damage.
Radiant
heating
system
piping
should include a means of
regulating
the boiler
return
water temperature
and
the system supply
temperature
(such
as
provided by
an
InJec-
tion pumping
control).
Boiler return
water
temperature
will
be
adequately
controlled using
the
methods shovm
in
this
manual
provided
the
system supply
temperature
is
relatively
cons
tent.
DO NOT
apply the methods of
this manual
if
the system
is
equipped
with an
outdoor
reset control.
Instead,
provtde
controls and
piping
which can
regulate
the
boiler
re-
turn water temperature
at
no less than
130°F regardless
of
system
supply
temperature.
Contact
your
Weil-Mcl.ain
representative
for
suggested piping
and
control
methods.
Failure to
prevent
cold return
water temperature
to
the
boiler
could
cause corrosion
damage to the
sections
or
burners,
resulting in possible
severe
personal
injury,
death
or
substantial property
damage.
Part Number 550-142-780/0712

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cgi-25Cgi-5Cgi-4Cgi-6Cgi-8Cgi-7

Table of Contents