Boiler Manual
lOb
Service
&
maintenance - annual start-up
<oont>
I&
WARNING
I
I&
WARNING!
Safely
retief nlves
should
be
reinspected AT
LEAST ONCE EVERY THREE
YEARS, by
a
licen~
plumbing con1ractor or
aulhorized
in-
spection agency,lo ensure
lhallhe product has nol
b«n affected by corrosive waler conditions
and 10
ensut'1'
lhal 1he
valve
and discharge
line
ha'"'
nol
b«n ahered or
lampered wilh
illegally. urtain
nalurally
occurring conditions
may
corrode
lhe
valve or
ils
componen1s o'-er
time,
t'1'ndering lhe
valve
inoper.ttive. SUch
conditions
are not
detect-
able
unlm the
valve and its components
are
physi-
cally t'1'moved and inspected.
This
inspection
must
only be conducted
by a plumbing contractor or
aulhorized
inspection
agency- nol by 1he owner.
Failure 10 reinspect lhe
boiler relief
valve as directed
could resuh
in
unsafe pi'1'Ssure buildup,
which
can
resuh in
severe
personal
injury,dealh or substantial
property damage.
Following
insl;tlhltion,
the
valve
lever must
be
operated AT LEAST ONCE A YEAR
10 ensure thai
wa1
erways
are
clear. Ceria
in naturally occurring
mineral
deposits m"y "dhere 10 lhe
va.
l
ve, rendering
il inopcral•vc.
When
manually operaling lhe
lever,
wa1
cr
will
disch"rge and precautions must
be
1aken
to avoid conlact wilh hoi
water
and
1
0 avoid waler
damage. Before
operating
lever, check to see
lhat
a
discharge line
is connected
10 lhis valve directing
the
flow
of
hoi water
from
lhe valve to
a
proper
place
of
disposal
olherwise
severe personal injury
may
result
H
no water
flows,
valve Is Inoperative.
Shu
I
down
boiler
until a new relief valve has been
inslalled.
Boiler
relie
f
va
lve
I.
Inspecl lhe relief \'ah·e and tift !he lever lo verify flow as in lhe
following warnings, excerpted from a 1'1'1ief vahT
manufacturer's
warning
label.
Before operating
any retief vah·e,
ensure
lhat it
is
piped wilh
its discharge
in a safe atn
to
0\'0id severe scald polential
Read
manual
Section
4
before proceeding
further.
2.
After following !he abo'"' warning
directions,
if
lhe 1'1'1ief val'"'
weeps
or will DOl seal properly, "'{'lace
the
relief yaJ,..,,
Ensure
1ha1 the
= n for t'1'lief vah-e "-etpmg
is
lhe
valve
and
DOl over-
prmurization
of
1he syslem
due
10
expansion
lank walerlogging
or
undersizing.
Figure
3
5
Relief
valve,
typical
Part Number
550-142-780/0712
0
Review with owner
I.
Review
lhe User's
Information
Manual
with
lhe
owner.
2.
Emphasize the need 10
perform
1he
mainlenance
schedule specified
in the
User's
Informati on
Manual
(and in Ibis manual
as well).
3.
Remind
lhe
owner of
1he need 10
call in a licensed
contractor
should
1he
boiler or sys1em exhibit any
unusual
behavior.
4.
Remind lhe
owner
to
follow
1he
proper shutdown
procedure
and
10 schedule
an annoal s1ar1-up
al the
beginning
of the
next
heating
season.
0
Cleaning boiler
heating surfaces
I&
WARNING!
The
boiler
contai
ns ceramic
fiber
and fiberglass
materials.
Usc
care
when
handling
these
materials per
instructions on
Page
70
of
this
manual.
Failure to comply
could
result
in
severe
personal
injury.
I
.
Shut
down
boiler:
Follow"To
TUm 011
Gao
to Applia
nce"
instruetions
on
boiler
and
Operating
lnstnsctlono.
Do
not
d
rain
boiler
unless
it
will
be exposed
1
0
frtezing temperatures.
I
(
using
antifreeze
in
sys:ten,
do not
drain.
2.
Follow
shutdown
procedure.
3.
Remove
venting
system
connection
to
boiler.
4. Remove
top j<>cket
panel.
Thrn bad<
insula
lion.
5. Remove
collector box/transition
assembly.
Oean sealant
from
assembly and
S«tiOII$.
6. Remove radiation plates hanging between sections.
7.
Remove
burners
&om
base.
Brush
and
vacuum burners
to
remove
all dust and tint.
Verify
that
aU
burner
ports
a"'
free
of
debris.
8.
Place .......,.pers in
base
of
boiler
to
collect
soot.
9.
Clean between
sect.
i ons with wile
flue
bruJb.
10.
Remove newspaper
and soot.
Vacuum
or
brush
base
and
sunounding
area.
11.
Reins~all
radiation
platO$.
U.
Replace
collector
box/transition
assembly. Seal
wilh
seaJ.
ant.
Obtain
gas-tighl
seal
to prevenl
flue
gas spillall"
and
carbon monoxide eml$$ions,
multing
in
sevtre persona]
injury
or
death.
13.
Replace
insulation
and
jacket
top
panel.
14.
Start
up
boiler following Section
7,
pagos
32-35
of
!his
manual
and
the
boiler
Operating
lnstructlont
. Excessive
sooting
indicate.
s
improper gas combus tion.
If
found
check for proper
combustion
and
mnkt ""Y
necess3ry
adjustmenrs.
49