Weil-McLain CGi Series 3 Installation And Maintenance Manual page 22

Gas-fired
Hide thumbs Also See for CGi Series 3:
Table of Contents

Advertisement

CG i
GAS-FIRED wATER BOILER- sERIEs a -
Boiler Manual
4c
22
Water piping - multiple zones
Piping multiple zones
Follow instructions on
pages
20 and 21
to
install
near-
boiler
or single-zone piping. (Also
refer
to
Piping
for
radiant heating
systems
or
converted gravity
sys-
tems, below,
if applicable.)
See Figure 18
or
Figure
19
to
complete installation.
Zoning
with circulators
(Figure 18)
(return temp over
130•F)
1.
Size
each
circulato
r
to
individual
circuit
require-
ments.
2. Do
not install
circulator
on boiler
(except
fo
r
primary/secondary piping).
3.
Install
isolation (balancing)
valves to
adjust
flow
to distribute heat
to
all zones.
Piping for radiant heating
systems or converted gravity
systems
Converted
gravity (or steam) systems
Whenever
possible, use
the
primary/secondary piping
shown
in
Figures
20 o
r
21
on
page
25. This
piping
de-
sign
allows
changing boiler
flow
rate
without
affecting
primary
circuit
flow rate.
If
Figures
20
or
21
cannot be used, use
the
boiler-by-
pass piping shown
in
Figure
22 or
Figure
23
o
n
page 27.
You
can
also use
the
piping
shown in
Figure
24
o
n
page
29
(system-bypass),
if
the reduced
flow
rate
in
the heating
system
will
not cause
heat
distribution
problems.
4. Install and wire
a
separate
relay
fo
r
each
zone
circulator.
I&
WARNING!
Failure
to prevent low
return
water
temperature to
the
boiler
c.
o
uld
cause
corrosion of
the
boiler
sec-
tions
or
burners,
resulting in
severe
personal injury, death or substantial
property
damage.
Zoning
with
zone
valves (Figure
19)
(return temp
over 130•F)
t.
Install
isolation (balancing)
valves to
adjust
flow to
distribute heat
to all zones.
2.
Provide
a separate 24-volt
transfo
m1er
to
power
the
zone
valves.
Size
the transformer to handle the total
rated
load
of all connected zone valves.
Radiant heating
systems
Preferably,
use
primary/secondary
piping,
as shown
in
Figures
20
or
21
on
page
25. Alternatively, use the
method of either
Figure
22
or Figure
23
o
n
page 27.
Do
not
use the
piping of
Figure
24
(system-bypass),
because
this
method does not control radiant
system
supply
temperature.
lA
CAUTlON
I
DO
NOT
connect
directly from
3-wire zone valves to
the T-T
termi-
nals on the
boiler. When
using 3-wire
zone valves,
install
an
isolation
relay.
Connect
the
zone va1ve end
switch
wires
to the isolation
relay
coil.
Connect
the
isolation
relay contact across the boiler
T-T terminals. Failure to comply
can
result
in
damage
to boiler
components
or cause unreliable operation, resulting
in
severe
property
damage.
If
radiant
system
tubing has
no
oxygen
barrier,
a
heat
exchanger
m ust be
used.
I&
WARNING!
Radiant heating
system piping sho
uld
include a
means of regulating
the
boiler
return
water
temperature
and
the
system supply
temperature
{such as provided
by an injection pumping
control).
Boiler return
water
tem
perature will be
adequately
controlled
using
the
methods
shown
in
this
manual
provided the system supply temperature
is relatively
constanL
DO
NOT
apply
the
methods
in
this
manual
if
the
system is
equipped with
an
outdoor reset
control.
Instead, provide controls
and
piping
which
can regulate the boiler return water
temperature
at
no
less than
130°F regardless of system supply
temperature.
Contact your
Weii-McLain
representative
for
suggested
piping and
control methods.
Failure to prevent
cold
return
water temperature to
the
boiler could cause
corrosion damage to the
sections
or
burners,
resulting
in
possible
severe
personal
injury,
death
or substantial property
dan1age.
Part
Number
550-142-780/0712

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cgi-25Cgi-5Cgi-4Cgi-6Cgi-8Cgi-7

Table of Contents