Weil-McLain CGi Series 3 Installation And Maintenance Manual page 48

Gas-fired
Hide thumbs Also See for CGi Series 3:
Table of Contents

Advertisement

CG i
GAS-FIRED wATER BOILER- sERIEs a -
Boiler Manual
lOb
48
Service & maintenance - annual start-up
<cont.)
0
Check/test
• • •
Gas
piping
1.
Sniff
near floor
and
around
boiler
area for any
in-
dication of a
gas
leak.
2.
Test
gas
piping using bubble test,
per
Section 5
of
this
manual,
if
there
is any
indication
of
a
leak.
Cold
fill
and
operating pressures
1.
While the
syste
m
is
cold,
note
the
pressure
reading
on
the boiler
pressure/temperature
gauge.
Verify that
cold
till pressure
is correct
2. Watc
h the pressure
as the boiler
and
system
heat
up
to ensure
pressure
rise
is normal. Too
high
a
rise
would
indicate
a
waterlogged or
undersized
expan
-
sion
tank.
Air
vents and air elimination
1.
Inspect
automatic air vents
(
if
used). Also inspect
air
separators
to
ensure
they
are operational.
2. The cap must
be
unscrewed
on
e
turn
to allow
air to
escape.
3.
See
Figure
34.1f
the air vent is
leaking, remove cap
A
and briefly push
valve
B
and
then release to
clean
the
valve seat.
4.
Replace
cap
A
by
tw isting
all the
way o
nto
valve
B
and then
unscrewing one
turn.
Figure 34
Limit
controls and cutoffs
1.
Inspect
and test the boiler limit
control
Verify
op-
eration
by
turning control set point below
boiler
temperature.
Boiler
should
cyde
off.
Return dial
to
original
setting.
2.
Inspect
and test additional
limit
controls
or low
wate
r
cutoffS
installed o
n
syste m.
Expansion
tank
1.
Expansion tanks
provide
space for
water
to move
in
an
out
as the heating
syste
m
water
expands
d
ue to
temperature increase or contracts as
the water
cools.
Tanks
may be
open,
dosed
or
diaphragm
o
r
bladder
type.
SeeSection4
of
this manual
for
suggested best
location
of
expansion
tanks
and
air
elimmators.
Open-type
-
located
above
highest radiator
or
baseboard
mlit,
usually in
the
attic
or
closet.
Has a
gauge glass and
overflow
pipe
to a
drain.
Closed-type
-
welded gas tight and
located
above
boiler.
Tank
is partially
tilled with
water,
leaving
an
air cushion
for expansion.
Make sure
tllis
type of
tank is
fitted with
a
tank
IHtlng,
such
as
the
B
&
G
Tank-Trot
or Taco
Taco-TroL
This
fitting
reduces gravity
circula-
tio
n
of
air-saturated tank water
back to the
system and
p revents
the air
fro
m
bubbling up
thro
ugh
the
water as
it
returns from the
syste m.
Do not use automatic air vents In
systems
with
closed-type
tanks.
The
air will
escape
fro
m
the
syste
m instead
of returning to
the
tank.
Eventually,
the tank will
wate rlog
and
no
longer
control
p ressurization. The
boiler
relief valve
will
weep freq uently.
Diaphragm-
or
bladder-type
-
welded
gas
tight
w ith
a
rubber
membrane to separate
the tank
pres-
surizing
air
an
d the
water.
May
be located
at
an
y
point
in
the
system, b
ut most
often
found near
the
boiler.
Systems
with
this type
of expan
sion
tank require
at
least
o ne
automatic
air
vent, preferab ly
lo-
cated
on top of
an air eliminator,
as shown
in
exan1ples
in
manual Section
4.
2.
If
relief
valve has
tended to
weep
freq uently, the
ex-
pansion
tank may be
wate rlogged o
r
u
ndersized.
Closed-type tank
-
tank
is
most
likely
water-
logged.
Install
a
tank
fitting
if
n ot
already
installed.
Then
check fill
level
per
fitting manufacture r's
instructions.
If till level
is
correct,
check tank
size
against manufacturers
instructions.
Replace
with
a
larger
tank
if necessary.
Diaphragm-
or
bladder-type
-
first, check tank
size to
be
sure
it
is
large
enough
for
the
syste m.
If
size is too
small,
add
additio
nal
tan
k(s) as
neces-
sary to
provide sufficient expansion
.
If
tank size is
large enough, remove
tank from
system
and
check
charge
pressure (usually
12
psig
for residential
ap-
plicatio ns).
l
f
tank
won'
t hold pressure,
membrane
has
been
damaged.
Replace tank.
Part
Number 550-142-780/0712

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cgi-25Cgi-5Cgi-4Cgi-6Cgi-8Cgi-7

Table of Contents