Weil-McLain CGi Series 3 Installation And Maintenance Manual page 35

Gas-fired
Hide thumbs Also See for CGi Series 3:
Table of Contents

Advertisement

CG i
GAS-FIRED wATER BOILER- sERIEs 3 -
Boiler Manual
7b
Start-up - operate boiler
(continued)
Start the boiler
Follow
the
Operating instructions
from Section 9c
to
start
the boiler.
See
Section 7c
if
boiler fails to
start.
Check system and boiler
t.
Check
system piping for
leaks.
If found,
shut
down
boiler
and repair
immediately.
2.
Vent
air
from
system
usin~
manual vents.
Air in
the
system
will interfere
with
circulatiOn
and
cause heat
distribution
problems
and
noise.
3.
Inspect
vent
system
thoroughly for
signs of
deterioration
from
corrosion,
physical
damage or sagging.
In
addition
-
Check
for gas-tight
seal
at
every
connection
and
seam.
Venting system must be sealed gas-tight
to
prevent flue gas
spillage
and carbon
monoxide emissions
which
will
result
in
severe
personal
injury or
death.
4.
Check
around
the boiler
for
gas
odor
following the
procedure
of Section 7a
of this manual.
5.
Verify operation per
Section
7b.
Perform check-out
pro-
cedure
in
Section
8,
and
fill in the
Installation
and servtce
certificate on
the
same
page.
Check burner flames
View
pilot and main flames
through
the inspection port
in
the
base
burner
shield.
Pilot burner flame
(Figure
28)
PROPER
pilot
flame
characteristics
t.
Blue
tlante.
2. Inner cone engulfing
pilot flame
sensor.
3.
Pilot flame
sensor
glowing cherry
red.
IMPROPER pilot
flame
charactf!f"istics
I.
Overtired
-
Large flame
lifting
or
blowing past pilot
tlante
sensor.
2.
Undertired
-
Small
flame. hmer
cone not
engttlfing
pilot
flame sensor.
3.
Lack
of
primary
air
-
Yellow flame tip.
4. Incorrectly
heated pilot
flame sensor.
Main burner flame
(Figure
29)
PROPER main burner flame characteristics
I. Yellow-orange streaks may
appear
(caused
by dust).
IMPROPER main burner flame
characteristics
I.
Overtired
-
Large flames.
2.
Undertired
-
Small
tlan1es.
3.
Lack
of
prinlary
air
-
Yellow tipping
on
flames
(sooting will occur).
Figure 28 Typical pilot burner flame
Figure 29 Typical
main
burner
flame
Tronsporont
btueflome
Inner
ftome
7c
Start-up - if boiler doesn't start
• • •
Check for:
I.
Loose
connections, blown
fuse
or
ser-
vice
switch off?
2.
High
linlit
switch
set
below
boiler water
temperature?
4.
Gas
not
turned
on
at
meter or boiler?
5.
Incoming
gas
pressure less than:
5"
w.c.
for
natural gas?
t
1"
w.c.
for propane gas?
71030
3. Thermostat
set
below
room
tempera-
ture?
6.
If
none of the
above
corrects the problem, refer to
Troubleshoot-
Ing, section
11
of this
manual.
Part
Number 550-142-780/0712
35