GAS-FIRED wATER BOILER- sERIEs a -
Boiler Manual
4b
Water piping - single-zone system
IAcAunoNI
Undersized expansion
tanks
cause
system
water to be lost
from
relief valve and makeup water
to
be added
through
till
valve.
Eventual
section failure can result
Diaphragm-type or bladder-
type expansion tank
(Figure 16)
t.
Ensure
expansion
tank size will handle ooiler
and
system
water
volume
and
temperature. Tank must
be
located
in
boiler return
piping as
close
to ooiler
as
possible, before
inlet
side
of
circulator.
See
tank
manufacturer's instructions for details.
2.
Install an
automatic
air
vent
as
shown.
Closed-type expansion tank
(Figure
17)
t.
Ensure expansion
tank
size will
handle
ooiler and
system
water volume
and
temperature.
See
tank
manufacturer•s
instructions
for details.
2.
Connect
tank
to 'h''
NPT
tapping
located
behind
supply
outlet,
using
'h"
NPT
piping.
Pitch
any
horizontal piping up towards
tank I
inch
per 5 feet
of
piping.
I&
WARNING!
Use
Figure
16
or Ftgure
17
only
for
single-zone systems
designed
for
return water
at least
I
30°F.
For systems with low
return
water
temperature
possible,
such
as converted gravity systems
and radiant heating systems,
refer to
the special
piping
suggestions of pages
24-29.
Failure
to
prevent
low return
water temperature to
the
ooiler could cause corrosion of
the
ooiler sections
or
burners, resulting
in severe personal injury, death or substantial property damage.
Figure
16
Diaphragm-
or
bladder-type
expansion
tank
-
Piping
to single-zone
system
using
diaphragm-type
or
bladder-type
expansion tank.
See
Table
6 for
piping
sizes.
Isolation
valve
Circulator
From
system
Cold
water
fill
To
DIAPHRAGM
expansion tank
and fittings
To
system
Automatic
air
vent
•Alternate
location
Figure
17
Closed-type expansion tank
-
Piping
to s ingle-zone system us ing
closed-
type expansion tank.
See
Table
6
for
piping
sizes.
Relief
valve
Circulator
From
system
CLOSED
type
expansion tank
--.......~.....-
Isolation
valve
To
system
•Alternate
location
Part
Number 550-142-780/0712
2