CG i
GAS-FIRED wATER BOILER- sERIEs a -
Boiler Manual
llc
Troubleshooting - control module lights
(cont.J
CHART 2 - TSTAT CIRC
&
POWER
lights flashmg
-
Usually indicates 48 VAC
on thermostat circuit (stray voltage)
-
I&WARNINGI
Electrical
shock
hazard
-
Wherever
you
see
.t.
TURN OFF
POWER&, follow the instructions.
Failure
to
follow
instructions could
result
in
severe
personal injury,
death,
or
substantial property
damage.
.
Disconnect
the
two
external
wires
connected
to the
boiler
.
If
a voltage
does occur under
any condition,
check
and
thermostat
leads (two black
low voltage
leads in
J-box).
correct
the
external
wiring. (This is
a common problem
Connect
a
voltmeter
across
these
two
incoming
wires
.
when
using
3-wire zone
valves.)
.
Close each thermostat, zone valve and
relay in the
external
.
Once
the
external thermostat circuit
wiring
is checked and
circuit one
at
a
time
and check
the
voltmeter
reading
corrected
if
necessary,
reconnect the
external thermostat
across
the
wires.
circuit
wires to the
boiler
thermostat
wires and allow
the
There should
NEVER
be
a voltage
reading .
boiler
to
cycle.
.
Did
you find
a
voffage
across
the
1\Vo
external
thermostat circuit
wires?
Yes
No
.
Leave
external
boiler thermostat connection wires
.
If no
vonage is
found under
any
condition of the
external
disconnected
from
boiler.
thermostat circuit,
connect the
two
boiler
thermostat
connection leads together
(or
jumper
the
boiler
aquastat
.
Troubleshoot the
external
thermostat
circuit
until you
find
T-T
terminals) .
the
source
of the stray
voltage.
(Pay
close
attention
to
the wiring
connections
to
3-wire zone
valves.)
~
.
Tum
off
power
to the boiler
for
1
minute.
.
Correct
the
problem
and repeat
the
voltmeter test above,
Tum on
power
and allow
boiler
to
cycle
.
.
verifying
there
is
no longer
a
voltage reading under
any
condition
in the
external thermostat
circuit.
Do
the
TSTAT
and
POWER
lights
sli//tiash?
.
An isolating
relay may be
required
.
-
No
I I
Yes
.
Boiler
should
now
operate
per
the
normal
sequence of
I:
Replace
control module
.
operation
shown
in
Figure
30, page 38.
Retest.
Part
Number
550-142-780/0712