LogicLinx Editor configuration

156
6 13/12/18 11:15:46 <Net OK > tom (SSH) -
originip="192.168.230.120" originMac="D8:9D:B9:00:0B:9C"
To configure the LogicLinx editor to use the secure connection:
1.
Start ConfigPro or SGConfig using "Run As Administrator".
2.
Open the Project containing the target D20MX device.
3.
If using ConfigPro, open the target D20MX device.
4.
Start the LogicLinx editor:
4.1.
If using ConfigPro, right click on the LogicLinx icon under the Data Translation
Applications tab and select Tools > LogicLinx Editor.
4.2.
If using SGConfig, click LogicLinx under the Automation Applications node of
the Applications List, and then click the LogicLinx Editor icon.
Result: The LogicLinx - Project Management window appears.
5.
Double click the program icon or its name (e.g. main).
Result: The LogicLinx Programs window appears.
6.
Click the Link Setup
Result: The PC-PLC link parameters dialog appears.
7.
Set the Communication port box to ETHERNET.
Result: The PC-PLC link parameters dialog appears as in the following screen:
8.
Change the Ethernet link parameters:
8.1.
Click the Setup button.
8.2.
Type 127.0.0.1 into the Internet address box.
8.3.
Type the port number you entered in step 2.2.of section "PuTTY configuration"
into the Port number box (for example: 1100).
Result: The ETHERNET link parameters dialog appears as shown in the following
screen:
8.4.
Click OK.
9.
Connect the debugger by clicking the Debug
APPENDIX E: SECURE CONNECTION FOR LOGICLINX
icon.