CHAPTER 5: CONFIGURING THE SOFTWARE
D20MX INSTRUCTION MANUAL
8.3.
Click the ribbon Configure group > Miscellaneous > Firmware Library.
Result: The Firmware Library window appears with the firmware definition
selected.
8.4.
Select Import.
Result: The Firmware Import window appears.
8.5.
From the Project Name drop down list, select D20MX01-14X or D20MX02-14X
based on the decision taken in step 2.
Result: The SAN0001 or SAN0002 firmware appears in the Firmware Available
list.
8.6.
Click OK.
Result: The Firmware Library window reappears with the SAN0001 or SAN0002
firmware in the list.
8.7.
Click Close.
Result: The Firmware Library window closes.
9.
Apply the firmware definition from the factory default configuration (if you had opted
to upgrade the firmware in ConfigPro, then this step is not necessary).
9.1.
Click the Project tab of the original D20 or D200 device configuration.
9.2.
Click the D20MX device.
9.3.
Click the ribbon Configure group > Edit > Properties.
Result: The D20MX Device Wizard Basic Settings window appears.
9.4.
Click Next until the Processor tab appears.
9.5.
Click the Firmware sub tab and Select.
9.6.
Select either SAN0001/14X or SAN0002/14X as per the decision taken in step 2.
Result: The Changing Device dialog appears. After some time it closes and the
D20MX Device Wizard appears.
9.7.
Click Finish.
Result: The D20MX Device Wizard closes.
10. Import the RADIUS roles from the D20MX default configuration into the D20MX device:
10.1. Double-click the D20MX device.
Result: The Application List popup appears.
10.2. Double-click the WESMAINT II+ application.
Result: The WESMAINT II+ table icon set appears.
10.3. Right-click the RADIUS Role Table icon and select Import.
Result: The Select source directory dialog appears.
10.4. Navigate to the DVD/CD drive or the ISO Image sub-folder nested two levels
into the folder extracted from the D20MX Documentation CD zip file. Then
navigate to Configuration Files > DefaultTableSettings > B014-1 Wesmaint
II+.
Result: The file B014RADR.CSV appears in the dialog.
10.5. Select the file named B014RADR.CSV, and click Open.
Result: The WESMAINT II+ table icon set re-appears.
10.6. Double-click the RADIUS Role Table icon.
Result: The RADIUS Role Table editor appears.
GE INFORMATION
79