CHAPTER 5: CONFIGURING THE SOFTWARE
Download image files
to the D20MX over a
serial link
D20MX INSTRUCTION MANUAL
5.
Click Configure ribbon group > Communications > Connect drop-down list > Tera
Term.
Result: Tera Term: New connection dialog appears
6.
Click Serial and select the communications port on your PC from the Port drop-down
list.
7.
Click OK.
Result: Tera Term: New connection dialog closes
Result: The Tera Term VT window appears
8.
Select Setup > Serial port...
Result: Tera Term: Serial port setup dialog appears
9.
Verify (or set) terminal communication settings as follows:
Setting
Value
Port:
COM1 or COM2, or as required by the computer you are using.
Baud Rate
baud rate of the D20MX (9600 or 19200 bps)
See "RS-232" on page 50 if you need to change the baud rate.
Data
8 bit
Parity
none
Stop
1 bit
Flow Control
Xon/Xoff
Transmit delay
0 msec/char; 0 msec/line
10. Click OK.
Result: The Tera Term settings are now configured.
Note: For a redundant system, download image files to the standby D20MX first. Then
switch-over and download image files to the new standby D20MX.
To download application and operating system image files to a D20MX module:
1.
Restart the D20MX.
Result: The startup messages appear.
2.
When the message "Press Ctrl-E to enter debug mode" appears, press Ctrl-E within 3
seconds.
Result: The login dialog appears.
3.
Log in:
For User: type a username that has Maintenance or Read/Write Access and press
Enter,
For Password: type the password and press Enter.
Result: The D20M> prompt appears.
4.
Optional: Speed-up communications to shorten download time.
Type Baud 115200 and press Enter.
Note: Select 57600 or 38400 if communications errors have occurred previously. Such
errors can occur due to the presence of ambient EMI, a long cable length, a PC with
communication limitations due to CPU speed or when using some serial to USB
adapters.
Result: The D20MX is now communicating at 115,200 baud.
4.1.
Select Setup > Serial port...
Result: Tera Term: Serial port setup dialog appears.
4.2.
Select 115,200 from the Baud Rate drop-down list.
GE INFORMATION