Hide thumbs Also See for D20MX:
Table of Contents

Advertisement

CHAPTER 5: CONFIGURING THE SOFTWARE

Apply HSP

D20MX INSTRUCTION MANUAL
2.
Open the project containing the configuration of the target D20MX device.
Result: The project's Main Page appears.
3.
Click on the D20MX device.
Result: The Communications group appears in the ribbon.
4.
Change the communication options to enable LAN communication with the D20MX.
Click the SGConfig ribbon Configure group > Communications > Options.
Result: The D2x Device Communication Options dialog box opens.
5.
Click the Interface tab the in the Connection Type group select iSCS LAN, then select
the Preferred LAN you wish to use, either LAN A or LAN B. This will most likely be LAN A.
Result: The iSCS LAN option is selected.
6.
Click OK to close the D2x Device Communication Options dialog box
Result: The dialog box is closed and the SGConfig ribbon Configure group >
Communications > Firmware transfer pick list is now active.
7.
Click the Configure group > Communications > Firmware transfer > HSP transfer.
Result: A dialog displaying a warning appears.
8.
Read the warning then click Yes to continue or No to abort the operation.
Result: If Yes is selected, then refer to the following table. If No is selected, the
operation is aborted.
Possible Result if Yes is Selected
Select Target IP Address dialog
appears
Login dialog appears
9.
Ensure the Standby IP checkbox is checked and if not, check it. In the associated IP
address field, ensure the IP address of the standby unit address is displayed and if
not, enter it.
Click Help for information on how to determine the Standby IP address.
10. Click OK.
Result: A login dialog appears.
11. Enter the User Name and Password of an account having SHELL access level of
Maintenance or higher and click Login.
Result: The Login dialog box closes, and the Transferring HSP dialog box opens. The
HSP transfer takes place. When the transfer is complete, the Transferring HSP dialog
box closes, and the HSP Transferred successfully dialog box opens.
12. Click OK to close the HSP Transferred successfully dialog box.
Result: The dialog box closes.
1.
Start SGConfig.
Result: The Welcome to SGConfig screen appears.
2.
Open the project containing the configuration of the target D20MX device.
Result: The project's Main Page appears.
3.
Change the communication options to enable serial communication with the D20MX.
3.1.
Click the SGConfig ribbon Configure group > Communications > Options.
Result: The D2x Device Communication Options dialog box opens.
When to expect this result
If the D20MX is configured for device
redundancy
If the D20MX is configured for standalone
operation
GE INFORMATION
Go to step
step 10
step 12