Configured Roles In The D20Mx - GE D20MX Instruction Manual

Hide thumbs Also See for D20MX:
Table of Contents

Advertisement

D20MX Processor
Appendix A: Default Role-Based
Access Control Model

Configured roles in the D20MX

D20MX INSTRUCTION MANUAL
When you configure the D20MX to use RADIUS, the D20MX must be configured with a set
of roles in the B014 RADIUS Roles Table (B014RADR) of the WESMAINT II+ application (Refer
to the B014-1NCG WESMAINT II+ for the D20MX Configuration Guide for more information).
The role is identified by a role ID, which is an integer number provided by the RADIUS
server.
The D20MX Default configurations D20MX01-14X and D20MX02-14X include a default
role-based access control model that meets the general rules shown in Table 21.
Table 21: General access control rules
Description
Can Change Passwords
Can Clear the Login Buffer
Can Change SCADA Settings
Can Download Firmware
Can Perform Operational Control (e.g. breaker
operation)
Can View Operational Data
Can Access Low Level "C" Shell
The Shell access level roles are provided in Table 22
Table 22: Shell access level
Description
Access Level
Administrator
(2)
Yes
No
Yes
Yes
Yes
Yes
Yes
Administrator
(2)
Read/Write
GE INFORMATION
Default Role-Based Access Control Model
Engineer
Operator
Observer
(1)
(3)
(0)
No
No
No
No
No
No
Yes
No
No
Yes
No
No
Yes
Yes
No
Yes
Yes
Yes
No
No
No
Engineer
Operator
Observer
(1)
(3)
(0)
Maintenance Read Only Read Only
99

Advertisement

Table of Contents
loading

Table of Contents