15.4. Review all warnings and make corrections as needed, reviewing the backup
copy to retrieve values that may have been replaced with default values during
the transfer.
16. Transfer the new configuration to the D20MX:
16.1. Click the Project tab of the original D20 or D200 device configuration
16.2. Click: the D20MX device.
16.3. Click the ribbon Configure group > Communications > Options.
Result: The Device Communication Options widow appears.
16.4. Click Interface tab > Connection Type.
16.5. Select Direct Serial and change the Communications Port to the serial port
that is connected to the D20MX.
Result: The Communications Options window shows that Connection Type is
set to Direct Serial and the Communications Port is set to the serial port
connected to the D20MX.
16.6. Click the Port Settings tab and set the Baud Rate to the baud rate of the
D20MX (9600 or 19200 bps - see "RS-232" on page 50 if you need to change the
baud rate), and select the Software Transmit and Software Receive check-
boxes. Then click OK.
Result: The D2x Device Communications Options dialog closes.
16.7. Physically connect the PC's serial port using the RS232 NULL modem cable to
either the front serial port of the:
– Standby D20MX, if the D20MX is configured for device redundancy, or
– Standalone D20MX, if the D20MX is configured for standalone operation.
16.8. Click the Configure ribbon group > Communications group > Connect.
Result: The Terminal Emulator window opens.
16.9. Login to the D20MX using the username admin and password changeme.
Result: The D20M> prompt appears.
16.10. Click the Configure ribbon group > Actions> Sync To.
Result: The Downloading Configuration File dialog appears showing the
progress of the download. At the conclusion, a Confirm dialog appears with
three buttons: Boot, Verify and Exit.
16.11. Click Boot.
Result: The D20MX reboots with the new configuration.
All users that existed in the transferred D20/D200 configuration now have the default
password: changeme. Change these passwords using the passwd command in the D20MX
Shell. Refer to the WESMAINT II+ for D20MX Configuration Guide B014- 0NCG for details of
this command.
If the D20MX was configured for device redundancy, once the sync to operation is
complete, the standby unit reboots and comes up again as standby with the new
configuration. If desired, switch over and synchronize the new configuration to the other
unit through the "Switch Over" and "Database Sync" functions available in the WESMAINT
System Functions menu. Refer to the WESMAINT II+ for D20MX User's Guide B014-0NUG
for details on these functions.
When transferring a redundant D20/D200, ensure the new D20MX standby IP addresses
do not conflict with other devices in the project. If they do, you may disable the standby IP
addresses or reassign them as described in "IP addresses" on page 47. If there are any
conflicts, the WESMAINT error log of the D20MX will log warnings such as the following:
1 ROOT N0: W001: IP of RDT1 same as CCUB
Where RDT1 is the host name of the device with a conflicting IP address.
CHAPTER 5: CONFIGURING THE SOFTWARE
GE INFORMATION
D20MX INSTRUCTION MANUAL