Field-replaceable fuses for the standard chassis-mounted Power Supplies are listed in
Table 7. These are the standard factory-installed fuses, unless otherwise specified. Always
replace with the same type and values of fuse.
Table 7: Field-replaceable fuses
Power Supply
Fuse
580 - 2004
F1
F2
580 - 2005
F1
F2
580 - 2006
F1
F2
580 - 2007
F1
F2
D20 modems (can be purchased separately) for communications to a host computer or to
other IEDs.
For example, WESDAC 202/V.23 is a 1200-baud Bell 202 or CCITT V.23 standard modem
designed for 300 to 1200 baud asynchronous operation on unconditioned lines and
supports the majority of SCADA/EMS applications. It is available in a 3U (GE part number
520-0120) vertical mount configuration in the D20 chassis; the 19 inch rack mount (GE part
number 520-0090) version is currently not supported.
Third-party modems can be used to meet specific requirements. These modems are
connected to the D20 via standard RS-232 connections. Contact GE Digital Energy for
more information on options.
GE INFORMATION
Fuse Function
Replacement Fuse
(¼inch by 1 ¼ inch Time Delay)
+DC Input
12 A / 250 V
-DC Input
12 A / 250 V
+DC Input
12 A / 250 V
-DC Input
12 A / 250 V
Line/+DC Input
4 A / 250 V
Neutral/-DC Input
4 A / 250 V
Line/+DC Input
4 A / 250 V
Neutral/-DC Input
4 A / 250 V