Figure 47a Terminal Function at 2-Wire Sequence Selection (setting: n036="Reverse RUN (2W)")
Figure 47b Terminal Function at 3-Wire Sequence Selection (setting: n036="FWD/REV Cmd (3W
· Local/Remote Selection (setting: "LOCAL/REMOTE Sel")
Selects whether the run command is received from the digital operator
or the control circuit terminal. Local/Remote selection is available only
while the inverter is stopped.
Open:
Run according to the setting of operation mode selection (n002).
Closed: Frequency reference and run command from the digital oper-
ator.
Example: Set n002 to "SEQ=TRM REF=TRM".
Open:
Frequency reference from control circuit terminals FV & FI,
and run command from control circuit terminals S1 and S2.
Closed: Frequency reference and run command from the digital oper-
ator.
· Serial Communication/Control Circuit Terminal Selection (setting:
"COM/INV Sel")
Selects operation reference by serial communication or by the control
circuit terminal. This selection is available only during stop.
Open:
run according to the setting of operation mode selection (n002).
Closed: Frequency reference and run command from serial communi-
cation.
FP5/GP5 User's Manual
Chapter 3 - Programming Features
S1
FWD Run/Stop
S2
REV Run/Stop
SC
Start
Stop
S1
Run Command
(Run when "Closed")
S2
Stop Command
(Stop when "Open")
S3
FWD/REV Run Selection
(FWD Run when "Open"
SC
REV Run when "Closed")
Inputs & Outputs
)")
79