2.4 OPERATION MODE SELECTION (n002, Oper Mode Select)
The FP5/GP5 has two operation modes: LOCAL and REMOTE
(see table below for description). These two modes can be selected by the
digital operator "LOCAL/REMOTE" key only when operation is stopped.
The operation mode selected can be verified by observing the SEQ and
REF LEDs on the digital operator (as shown below). The operation mode
is set to REMOTE (run by control circuit terminals FV and FI frequency
reference and run command from control circuit terminals) prior to ship-
ment. Multi-function contact inputs from control circuit terminals S3 to
S6 are enabled in both operation modes.
· LOCAL:
· REMOTE: Master frequency reference and run command can
Parameter n111, LOC/REM Change, will determine if the inverter will
acknowledge a previously closed run input during a switchover from
LOCAL to REMOTE mode.
· When n111 is set to "Cycle Extern Run", the inverter will not start
if the run input is closed during the transition from LOCAL to
REMOTE.
· When n111 is set to "Acept Extern Run", the inverter will immedi-
ately start if the run input is closed during the transition from
LOCAL to REMOTE.

Operation Mode Selection

LED
Display
0
SEQ=OPR REF=OPR
1
SEQ=TRM REF=OPR
2
SEQ=OPR REF=TRM
3
SEQ=TRM REF=TRM
4
SEQ=OPR REF=COM Operation by run command
5
SEQ=TRM REF=COM Operation by run command
6
SEQ=COM REF=COM Operation by run command
7
SEQ=COM REF=OPR Operation by run command
8
SEQ=COM REF=TRM Operation by run command
FP5/GP5 User's Manual
Both frequency reference and run command are set
by the digital operator. Remote SEQ and REF LEDs
go OFF.
be selected as described in the table below.
LCD
Operation Method Selection SEQ
Display
Operation by run command
from digital operator
Operation by run command
from control circuit terminal
Operation by run command
from digital operator
Operation by run command
from control circuit terminal
from digital operator
from control circuit terminal
from serial communication
from serial communication
from serial communication
Chapter 2 - Operation

Operation Mode Selection

REF
Reference Selection
LED
LED
OFF Master frequency reference
OFF
from digital operator
ON Master frequency reference
OFF
from digital operator
OFF Master frequency reference
ON
from control circuit terminals
FV and FI
ON Master frequency reference
ON
from control circuit terminals
FV and FI
OFF Master frequency reference
ON
set by serial communication
ON Master frequency reference
ON
set by serial communication
ON Master frequency reference
ON
set by serial communication
ON Master frequency reference
OFF
from digital operator
ON Master frequency reference
ON
from control circuit terminals
FV and FI