Frequency Agree Set Point (n075, Freq Det Level)
When multi-function contact output selections n041 or n042 are set to "Freq
Det 1" or "Freq Det 2", frequency detection is enabled. This function is acti-
vated when the output frequency is above or below the frequency agree set
point (n075).
· Output frequency ≤ Frequency agree set point
Set n041 or n042 to "Freq Det 1".
Output Frequency
Frequency Detection
Signal
· Output frequency ≥ Frequency agree set point
Set n041 or n042 to "Freq Det 2".
FP5/GP5 User's Manual
Chapter 3 - Programming Features
Release Width
+2Hz
ON
Figure 26 Frequency Agree Set Point Example
(Fout

Frequency Agree Set Point)

Frequency Agree Set Point

n075
Output Frequency
Frequency Detection
Signal
Figure 27 Frequency Agree Set Point Example
(Fout ≥ Frequency agree set point)
FP5/GP5Operation
Frequency Agree Set Point
n075
ON
Release Width
-2Hz
ON
57