Frequency Agree Set Point (n075, Freq Det Level)
When multi-function contact output selections n041 or n042 are set to "Freq
Det 1" or "Freq Det 2", frequency detection is enabled. This function is acti-
vated when the output frequency is above or below the frequency agree set
point (n075).
· Output frequency ≤ Frequency agree set point
Set n041 or n042 to "Freq Det 1".
Output Frequency
Frequency Detection
Signal
· Output frequency ≥ Frequency agree set point
Set n041 or n042 to "Freq Det 2".
FP5/GP5 User's Manual
Chapter 3 - Programming Features
Release Width
+2Hz
ON
Figure 26 Frequency Agree Set Point Example
≤
(Fout
Frequency Agree Set Point)
Frequency Agree Set Point
n075
Output Frequency
Frequency Detection
Signal
Figure 27 Frequency Agree Set Point Example
(Fout ≥ Frequency agree set point)
FP5/GP5Operation
Frequency Agree Set Point
n075
ON
Release Width
-2Hz
ON