To operate the inverter with a frequency reference of 50% to 100% at a
0 to 10V input:
Figure 31 Frequency Signal Adjustment Example - 0 to 10V input
Gain: Parameter n048 = "100"
Bias: Parameter n049 = "50"

Jog Operation

Multi-function inputs (Terminals S2 to S6) can be programmed to func-
tion as a jog reference selection. Operation can then be enabled at the jog
frequency reference set in parameter n030 by activating this input. A
"RUN" command must also be given to start the inverter. When multi-
step speed references 1 or 2 are input simultaneously with the jog fre-
quency reference, the jog frequency reference has priority.
Name
Jog frequency reference
Multi-function contact input
selection (S2 to S6)
Jump Frequencies (n062, Jump Freq 1; n063, Jump Freq 2,
This function enables the "jumping" of critical frequencies so that sys-
tems can operate without excessive vibration or noise. Setting the value to
0.0Hz disables this function.
Set jump frequency 1 or 2 such that n062 ≤ n063. If this condition is not
satisfied, the inverter displays the parameter setting error "OPE6".
60
Max. Output
Frequency (100%)
50%
0V
10V
Parameter No.
n030
n036, n037, n038, n039, n040
n064, Jump Bandwidth)
Output Frequency
n063
n062
n064
n064
Frequency
Reference
Figure 32 Jump Frequencies
Setting
6.0Hz (Factory default)
Set to "Jog Command" for any
parameter.
FP5/GP5 User's Manual