Motor Current
n073
Output Frequency
In the constant output area [output frequency ≥ base frequency (n013)],
the current limit level during acceleration is changed by the following
equation:
Current Limit Level During
Accel in Constant Output Area
· Stall Prevention Level During Running (n074, StallP Run Level)
The stall prevention level during running can be set in units of 1%
(inverter rated current = 100%).
Factory setting: kVA dependent
A setting of 200% disables current limit during running. During speed
agree, if the output current exceeds the value set for parameter n074,
then deceleration is initiated.
While the output current exceeds the value set for n074, deceleration
continues. When the output current goes below the value set for param-
eter n074, acceleration begins at the normal acceleration rate bringing
the motor to the set frequency.
Motor Current
n074
Output Frequency
FP5/GP5 User's Manual
Chapter 3 - Programming Features
Time
Time
* Holds the output frequency
*
Figure 20 Stall Prevention During Acceleration
Current Limit Level During
×
=
Acceleration (n073)
Time
Time
* Decreases the output frequency
*
Figure 21 Stall Prevention During Running
FP5/GP5 Operation
to limit the load current.
Base Frequency (n013)
Output Frequency
to limit the load current.