Clearances

When mounting the FP5/GP5, allow sufficient clearances for effec-
tive cooling as shown below:
Notes:
1) The required clearances at the top, bottom, and both sides of the inverter are the same
for both open chassis and NEMA 1 enclosures.
2) For inverter models 25HP and less (230V & 460V), remove the top and bottom covers
to convert NEMA 1 units to open chassis
3) Allowable intake air temperature:
Open chassis:
NEMA 1:
4) When mounting units in an enclosure, install a fan or other cooling device to limit the
air temperature within the inverter to below 113°F (45°C).
FP5/GP5 User's Manual
Chapter 1 - Receiving & Installation
W1
W
Front View
Figure 7 FP5/GP5 Dimension Diagram
1.97in (50mm)
4.72in (120mm)
1.18in (30mm)
4.72in (120mm)
1.97in (50mm)
Front View
Figure 8 FP5/GP5 Clearances
14°F to 113°F (-10°C to +45°C)
14°F to 104°F (-10°C to 40°C)
Mounting
D
Side View
Air
Air
Side View