4.2.2

PU Jog operation

Hold down
or
release it to stop.
Jog operation cannot be performed in the following
cases:
· During motor operation
· The Pr. 15 Jog frequency is less than the Pr. 13
Starting frequency.
Example: To operate at the PU Jog running
frequency of 8Hz
Step
Operation Procedure
1
Switch to the PU
operation mode.
If the operation mode
indication is not [PU], refer
to page 82 and switch to the
PU operation mode.
2
The frequency for Jog
operation can be set with Pr.
15 Jog frequency and the
acceleration/deceleration
time with Pr. 16 Jog
acceleration/deceleration time
both in the parameter unit.
(Refer to page 33 for the
parameter setting method.)
<Initial value>
·
·
Pr. 15 5Hz
Pr. 16 0.5s
to perform operation, and
Image
1. Power on
Operation mode check
ON
READ:List
0.00
--- STOP PU
2. Parameter setting
How to Operate PU Operation
Step
Operation Procedure
3
Press
The PU Jog operation mode
is selected, and the PU Jog
frequency setting screen
appears on the display.
To change the frequency,
enter the value and press
.
4
Press
The display changes to the
monitor screen. Hold down
the key to perform operation
and release it to stop.
5
Press
Hz
The inverter exits from the
Jog operation mode and
returns to the ordinary PU
operation mode.
REMARKS
·
The Jog operation mode may also be selected from
. (Refer to page 61)
·
When FR-PU07BB is used in the battery mode (the
inverter power is OFF), the operation is not available.
Image
, then
.
3. Jog operation mode selection
or
.
4. Operation
(or)
.
5. Exit from jog operation mode
PU/JOG
SET
8.00Hz
0~400Hz
Freq Set
SET
0.00Hz
0~400Hz
4
85