Adjustment of the Frequency Setting Signals "Bias" and "Gain"
• Setting of the frequency setting voltage gain
9
Press
, then
The present Pr. 903 setting
value appears.
When the set voltage is
changed, the % value also
changes.
The value selected in Pr. 73
(5V in this example) is 100%.
10
Enter
.
Set the gain frequency at
50Hz.
11
Press
.
The cursor (
) moves to the
set voltage.
Voltage need not be applied
across terminals 2-5.
12
Enter
.
Input 5V to set gain.
52
.
903 Ext2gain
60.00Hz
1)
97.1%
Ext
80.0%
2)
1) The previous
setting is
displayed.
2) The present set
voltage across
terminals 2-5 is
displayed in %.
903 Ext2gain
50Hz
97.1%
Ext
80.0%
903 Ext2gain
50.00Hz
97.1%
Ext
80.0%
903 Ext2gain
50.00Hz
100.0%
Ext
80.0%
13
Press
.
The gain frequency is set at
50Hz.
Setting is completed as
shown below:
f
50Hz
10Hz
0
(0%)
(100%)
The adjustment of the frequency setting voltage
bias and gain is complete.
REMARKS
1
The current input (Pr. 904, Pr. 905) can also be
adjusted using a similar procedure.
2
The Pr. 903 Terminal 2 frequency setting gain remains
unchanged even if the Pr. 20 Acceleration/
deceleration reference frequency setting is changed.
3
A narrow calibration (command) value set using Pr.
902 and Pr. 903 (Pr. 904 and Pr. 905) will result in "Incr
I/P" and disable write.
903 Ext2gain
50.00Hz
100.0%
Completed
V
5V