(2) Verifying the parameters
All the parameter settings stored in the FR-PU07 are verified with those which are stored in the inverter.
REMARKS
Verification cannot be performed between different inverter series.
1
Refer to page 77 and copy the parameter settings of
the verify source inverter to the FR-PU07.
2
Connect the FR-PU07 to the inverter to be verified.
3
Press
.
The function menu appears.
4
Select the "multiple
copies".
/
Using
, move the
cursor to "12 PRCpy set" and
press
.
5
Select the copy area.
Point the cursor to the copy
area that stores the
parameter settings required
verification, and press
1 MONITOR
2 PU Oper
3 Pr.List
4 Pr.Clear
9 S/W
10 Selectop
11 Option
12 PRCpy set
1 Copy area 1
2 Copy area 2
3 Copy area 3
.
Operation Procedures for Functions
6
Select the "Verifying".
/
Using
, point the
cursor to "3 Verifing" to press
.
7
Verification of the parameter
settings is selected, and the
confirmation screen for
verification is displayed.
8
Press
.
Start verification of parameter
settings stored in the FR-
PU07 and parameter settings
of the inverter.
Copy area 1
1 Read VFD
2 Write VFD
3 Verifing
012
Verify Area 1
WRITE:Executing
ESC:Cancel
Param Copy
Verifying
Verifying
Please Wait
3
79