Calibration of the Meter (Frequency Meter)
4
Enter
and press
.
60Hz is set.
5
Press
.
Forward rotation is performed
at 60Hz. You need not
connect the motor.
6
Using
/
, adjust the meter pointer to a
predetermined position.
The meter pointer moves. (It takes a long time before
the pointer moves.)
7
Press
.
Calibration is complete.
8
Press
to return to the
main monitor screen.
44
(2) When calibrating output current
For the output current or another item, which does
901 AM Tune
Run Inverter
not easily point 100% value during operation,
60Hz
adjust the reference voltage output, then select the
PU
item to be displayed.
901 AM Tune
MntrF 60.00Hz
<WRITE>PU
901 AM Tune
Completed
<MONITOR>
READ:List
60.00
Hz
STF FWD PU
1
Press
.
The frequency setting screen
appears, and operation mode
changes to PU operation mode.
2
Press
.
The parameter unit is in the
parameter setting mode.
3
Enter
and
press
.
The present Pr. 158 setting
appears.
4
Enter
and press
The setting of reference
voltage output is complete.
5
Press
.
The parameter unit is in the
parameter setting mode.
Freq Set
SET
0.00Hz
0~400Hz
SETTING MODE
0~9:Ser Pr.NO.
Select Oper
158 AM set
1
.
158 AM set
21
21
Completed
SETTING MODE
0~9:Ser Pr.NO.
Select Oper