4.3.2

Ventilation

Caution:
In order to avoid damage to the boiler, it is necessary to prevent the
contamination of combustion air by chlorine and/or fluoride
compounds, which are particularly corrosive. These compounds are
present, for example, in aerosol sprays, paints, solvents, cleaning
products, washing products, detergents, glues, snow clearing salts,
etc. Therefore:
- Do not pull in air evacuated from premises using such products:
hairdressing salons, dry cleaners, industrial premises (solvents),
premises containing refrigeration systems (risk of refrigerant
leakage), etc.
- Do not stock such products close to the boilers.
If the boiler and/or peripheral equipment are corroded by such
chloride or fluoride compounds, the contractual guarantee
cannot be applied.
A
The combustive air must reach the burner from the
front.
The location of air inlets in relation to the high ventilation openings
shall ensure that the air is renewed in the entire volume of the boiler
room.
Please refer to the prevailing regulations in your country.
14
France
Direct air inlet:
Boiler with nominal output between 25 and 70 kW in accordance
with DTU 61.1 (NF P 45-204).
In the case of a direct air inlet, the compulsory cross section of
the air vent must be of a minimum surface area of 70 cm
Boiler with nominal output greater than 70 kW in accordance
with DTU 65.4 (NF P 52-221).
Upper and lower air vents compulsory.
- Upper air vents: Cross section equal to half the total cross section
of the flue gas pipes with a minimum of 2.5 dm
- Lower air vents:
Direct air inlet:
(
S dm
P = Installed power in kW
GAS 360 S
2
.
0 86P
,
2
)
------------- -
20
04/01/11 - 300005180-001-C