Setting The Injector Pressure - REMEHA GAS 360 S Installation And Service Manual

Gas-fired boilers
Hide thumbs Also See for GAS 360 S:
Table of Contents

Advertisement

5.4.3

Setting the injector pressure

Turn the boiler on.
.Check points before commissioning (page: 19)
Commissioning procedure (page: 19)
The pressure must be set by a qualified professional.
04/01/11 - 300005180-001-C
Pressure socket
- Connect the manometer to the left or right pressure outlet on the
manifold.
- Set the boiler thermostats to maximum.
- Unscrew the protection cap on each valve.
- Set the pressure on the left valve and the right valve using the
screw which can be found under the protective plug.
Pressure setting and marking of calibrated injectors (page:23)
The pressure must be the same on both pressure outlets on
the manifold.
- Replace the protection caps.
When replacing a gas valve:
Check that the screw under the protection cap is fully tightened.
Carefully set the pressure and progressivity at the opening as
described in this chapter.