7.2 Maintenance

Carry out the following maintenance at least 1 time a year:

- Cleaning main burner and ignition burner

- Cleaning of the heating body
- Cleaning painted surfaces
7.2.1
Cleaning main burner and ignition burner
Cut the electricity and gas supply to the boiler.
Main burner
Clean the burner trains (slits) using a soft brush, a short-
handled brush or a vacuum cleaner.
Do not use a metal brush.
On reassembly, replace the burner earth wire fixed to the right
holding nut on the burner drawer.
Ignition burner
Clean the filter and the ignition burner injector.
Remove ionization probe 1 and the earth electrode 2 deposits
(for example using sand paper).
Carry out a gas tightness check.