Gas Connection; Connection To A Chimney - REMEHA GAS 360 S Installation And Service Manual

Gas-fired boilers
Hide thumbs Also See for GAS 360 S:
Table of Contents

Advertisement

4.5 Gas connection

J
Gas inlet R1

4.6 Connection to a chimney

Good
Poor
A
40 mm (minimum)
The appliance must be installed in accordance with the Codes of
Practice using a leak proof pipe made of a material capable of
withstanding hot combustion gases and any acidic condensation.
The pipe must be laid out to allow any likely condensation to drain.
It must be in accordance with existing regulations for pipes used for
this purpose. Standard meshed connection pipes are to be avoided.
The pipe connecting the outlet conduit must also be as short as
possible and without a reduced diameter.
The vertical section of the draught diverter outlet must be a minimum
length 3x the diameter of the nozzle before an elbow joint is fitted.
The pipe must have a diameter not less than the heater's nozzle
diameter along its whole length. This pipe must be able to be easily
disassembled and must not have a sudden change in diameter.
The outlet conduit must be maintained in a good condition, checked
and cleaned at least once a year.
04/01/11 - 300005180-001-C
It is necessary to abide by the prevailing instructions and regulations.
Each time, a blocking tap will be located as near as possible to the
heater. A gas filter must be fitted to the boiler inlet.
France
Pipe diameters must be defined in accordance with ATG's
(Association Technique de Gaz) B171 specifications.
Other countries
The diameters of the pipes must be defined in accordance with the
standards in force in your country.
GAS 360 S
17