5. Installation
20
5.3.3.
(1)
844
C003075-E
n Connection to a chimney
Do not obstruct the air inlets in the room (even partially).
The compulsory cross section of aeration vents in the premises in
which the boiler is installed must comply with the standards current
in the country.
n Forced flue connection
If the discharge of combustion gases and the intake of combustive air
are done using a concentric flue, ventilation of the boiler room is only
necessary if a mechanical connector is fitted to the gas supply (as per
the description in the DTU 61.1 standard).
CALORA TOWER GAS 15S EX CALORA TOWER GAS 25S EX

Ventilation

Minimum recommended distance
CAUTION
In order to avoid damage to the boiler, it is necessary to
prevent the contamination of combustion air by chlorine
and/or fluoride compounds, which are particularly
corrosive. These compounds are present, for example, in
aerosol sprays, paints, solvents, cleaning products,
washing products, detergents, glues, snow clearing salts,
etc. Therefore:
Do not pull in air evacuated from premises using such
4
products: hairdressing salons, dry cleaners,
industrial premises (solvents), premises containing
refrigeration systems (risk of refrigerant leakage),
etc.
Do not stock such products close to the boilers.
4
If the boiler and/or peripheral equipment are corroded
by such chloride or fluoride compounds, the
contractual guarantee cannot be applied.
CALORA TOWER GAS 35S EX