5.4 Gas settings

GAS 360 S boilers are delivered preset for operation on natural
gases of H/E groups.
For operation on another group of gases, carry out the following
operations.
5.4.1

Changing the burner injectors

5.4.2

Changing the ignition burner injector

20
These actions must be carried out by a qualified
technician.
Cut the electricity and gas supply to the boiler.
Lift out the injector with a number 12 spanner assemble the new
injectors with their new joint.
Natural gas H
Propane
Assembly:
Correctly replace the seals.
First tighten the injectors by hand and carefully lock them using
a spanner.
Carry out a gas tightness check.
Unscrew the connecting nut (14 spanner)
Pull the gas supply pipe towards yourself
Take out the ignition burner nozzle
Fit the new nozzle
Natural gas H
Propane
Re-attach the supply tube (14 spanner)
Carry out a gas tightness check.
GAS 360 S
Nozzle marking
257B
160B
Nozzle marking
40
30
04/01/11 - 300005180-001-C