Entering Base And Span Values; Entering Error Handling - GE UTX878 Ultrasonic User Manual

Ultrasonic flow transmitter
Table of Contents

Advertisement

Entering Base and Span
Values

Entering Error Handling

Configuring Meter Data
1. In the Loop option, press [ ] and [ENT] to enter the Base option.
2. The Base window opens. Use the arrow keys to enter the desired
base (4 mA) value for the analog output, and press [ENT].
3. The UTX878 returns to the Loop menu. Press [ ] and [ENT] to
enter the Span option.
4. The Span window opens. Use the arrow keys to enter the desired
span (20 mA) value for the analog output, and press [ENT].
1. The UTX878 returns to the Loop option. Press [ ] and [ENT] to
enter the Error Level option.
2. The screen displays a list of error options as defined in Table 4-1
below and Table 4-2 on the next page. Scroll to the desired option
and press [ENT].
Table 4-1: Error Options and Responses
for a 1-Channel/Path Meter
Option
Output Response
Hold Value Holds the last "good"
reading.
Force HI
Forces the outputs to the
high set point.
(20 mA)
Force LO (4
Forces the outputs to the
low set point.
mA)
Force HH
Forces the outputs ≈10%
(22 mA)
above the high set point.
Force LL
Forces the outputs ≈10%
(3.8 mA)
below the low set point.
Force Value Forces the outputs to a
preprogrammed value.
If you select Force Value (as shown in Table 4-1 above), the
meter asks for a specific value. Use the arrow keys to enter the
desired value, and press [ENT].
March 2004
Totalizer Response
Holds the last "good"
reading and continues to
totalize, based on that
reading.
Stops totalizing.
Stops totalizing.
Stops totalizing.
Stops totalizing.
Stops totalizing.
4-3