Torque Control; Electronic Thermal Overload - Omron 3G3MX2 Quick Start Manual

Born to drive machines; 200 v class three-phase input 0.1 to 15 kw; 200 v class single-phase input 0.1 to 2.2 kw; 400 v class three-phase input 0.4 to 15 kw
Hide thumbs Also See for 3G3MX2:
Table of Contents

Advertisement

PROGRAMMING MX2
Parameter
b022
Torque limit 2 (rev/regen.)
b043
Torque limit 3 (rev/power)
b044
Torque limit 4 (fwd/regen.)
b045
Torque LAD STOP selection
100% torque is referred to inverter rated current, absolute torque value is up the motor to be combined.

3.17 Torque control

Torque control in open loop could be achieve with following parameters. 100% torque is referred to inverter rated current but
absolute torque value depends on the motor connected. It has limited accuracy and working range so is recomended only above
15 - 20Hz and over 20 - 30% of the motor torque capacity.
Parameter
P033
Torque command input selection
P034
Torque command level input
P036
Torque bias mode selection
P037
Torque bias value setting
P038
Torque bias polar selection
P039
Speed limit of Torque control (Forward
rotation)
P040
Speed limit of Torque control (Reverse
rotation)
P041
Speed / Torque control switching time
To enable the torque control is necessary to assign the "ATR" (Enable torque command input) to one of the multi-function inputs
and set it to ON. When the input is OFF the inverter will work in speed mode.
At low speed, small torque command or 4 quadrant control applications the perfomance of this function will be limited due the
open loop system.

3.18 Electronic thermal overload

The thermal overload detection protects the inverter and motor from overheating due to an excessive load using a current
inverse time curve to determine the trip point. The characteristic curve depends on dual rate setting in b049 and is unique for
both inverter and motor but reduction rate depending on the frequency could be selected in parameter b013.
b049=00
Trip time (s)
60
3.0
0
MX2 Quick Start Guide
Parameter name
Torque limit level in reverse regen. quadrant, range is 0 to 200% / no(disabled)
Torque limit level in reverse powering quadrant, range is 0 to 200% / no(disabled)
Torque limit level in forward regen. quadrant, range is 0 to 200% / no(disabled)
00
Disable
01
Enable
Parameter name
00... Analog voltage input [O]
01... Analog current input [OI]
03... Operator, 06...Option
Set range is 0~200%
00... According to the sign
01... According to the rotation direction
05... Option
Range is -200~200%
00... No bias
01... Operator
Set range is 0.00~120.00Hz
Set range is 0.00~120.00Hz
Set range is 0 to 1000 ms
(HD )
Percentage of
109%
150%
200%
b012/b212
Description
Description
b049=01
(ND )
Trip time (s)
60
0.5
0
116%
120%
150%
Percentage of
b012/b212
31