RE 30126-01-B/08.07 | Manual
Fault Status
n
ABS(LVDT)<=WINDOW
The spool is in the zero position. A tolerance for the zero position (here
"WINDOW") of the valve is needs to be configured.
n
Fault Status
The present fault is output as a combination of pulses. The output can be fed to
an optional output DO1 to DO7 depending on the configuration.
Depending on the selection of the pull-down menu the entry fields „WINDOW" and
„Debounce" appear. "WINDOW" has to be configured with the value for the selected
condition. "Debounce" has to be configured with the time the fault condition has to be
present before the Digital Output is set.
The last column presents the opportunity to invert the signal.
Fault code
1
Range error for analog input Al1.
2
Range error for analog input Al2.
3
Range error for analog input Al3.
4
Range error for analog input Al4.
5
Range error for analog input Al5.
6
Range error for analog input Al6.
7
Not used.
8
Not used.
9
LVDT secondary side.*
10
Not used.
13
Short Circ Solenoid.*
14
LVDT primary side.*
15
Not used.
16
Not used.
17
Error block timeout.
18
Not used.
19
Block error.
20
Control error Loop 1.
21
Control error Loop 2.
22
Not used.
23
Parameter file checksum error .
24
Not used.
25
24V supply voltage fault.
26
Reference voltage fault.
27
Fault short-circuit of digital output DO1.
28
Fault short-circuit of digital output OK.
29
Fault short-circuit of digital output DO2.
Hydraulics | Bosch Rexroth AG
BODAC – Menu Description 5
Fault
64/76