Configure Analog I/O - Inputs - REXROTH VT-VRPD-2 Start-Up And Operation

Digital valve amplifier for valve types 4wre 6, 10 component series 2x
Table of Contents

Advertisement

RE 30126-01-B/08.07 | Manual

Configure Analog I/O - Inputs

min Fault
max Fault
max Unit
The following parameters can be used to configure the Analog I/O – Inputs:
The value range of the signal in [%] is set in the „Range" column. If the selection +/-
Range
10V is made in the „Type" column a signal of (-10V) corresponds to a signal of (-
100%) when the range setting is +/-100%.
The „Min" value sets the minimum fort he input signal. Depending on the setting of
Min
„Type" and „Range" this value is translated to the minimum value of the „Range"
setting.
If for example you enter -5V , with Type = +/-10V and Range = +/- 100%, a signal of -
5V is interpreted as -100%.
The „Max" setting is the opposite of the „Min". If +9V is entered a signal of +9V is
Max
interpreted as 100%.
If the value falls below the entered value, BODAC uses the „Status" window and the
„Status bar" to indicate that a fault has occurred. Specifying the error response is
done in the "Faults" window.
If the value exceeds the entered value, BODAC uses the „Status" window and the
„Status bar" to indicate that a fault has occured. Specifying the error response is done
in the "Faults " window.
The „max Unit" specifies the conversion from Range [%] to Units [Unit].
Fields that can not be modified are grayed-out.