Avaya S8700 Installation Instructions Manual page 118

Installing an avaya s8700 media server with an avaya g650 media gateway
Hide thumbs Also See for S8700:
Table of Contents

Advertisement

The single-phase, 4-wire, 120/240 VAC supplying 208 — 240 VAC can supply 60 Hz power to the AC
load.This source has 2 hot wires, 1 ground wire, and 1 neutral wire (J58890CE).
Either of these power sources can supply 50 Hz power to the AC load:
Non-US 5-wire, Y, 220/380 VAC. This source has 3 hot wires, 1 neutral wire, and 1 ground wire.
Non-US Delta, 4-wire, 220 or 240 VAC. This source has 3 hot wires and 1 ground wire (describes
the power sources and required AC input power).
Table 7: AC power sources and plug type
Power distribution unit
AC power distribution
(J58890CE) media gateway
Grounding an AC-powered media gateway (J58890CE)
Grounding is relatively simple for an AC-powered media gateway. Basically, the media gateways connect
to the single-point ground terminal block located at either the AC load center or to a separate single-point
ground block wired to the AC load center (or optional AC protector media gateway).
The approved ground wire must be a green (or green with yellow stripe), 6 AWG (#40) (16 mm
copper, stranded wire.
Bond all approved grounds at the single-point ground to form a single grounding electrode
system.
Grounding an AC load center 50 feet (15.2 meters) or less from media gateway
1
At the bottom rear of the first media gateway, connect a 6 AWG (#40) (16 mm
GROUND wire to the media gateway ground terminal block. See
gateway grounding wiring diagram,
2
Route the media gateway GROUND wire to the single-point ground block at the AC load center
and connect.
3
At the bottom rear of the next media gateway (if provided), connect a 6 AWG (#40) (16 mm
media gateway GROUND wire to the media gateway ground terminal block.
4
Route the media gateway GROUND wire to the single-point ground block at the AC load center
and connect.
5
Repeat connecting each media gateway to the single-point ground block.
118
Power sources
Single-phase 120 VAC with
neutral
Single-phase 240 VAC with
neutral, or single phase of 3-
phase, 208 VAC with neutral
NOTE:
If the media gateway is located remotely (in a separate room or building), connect the
media gateway GROUND wire to an approved ground.
Installing the Avaya S8700 Media Server with an Avaya G650 Media Gateway
on page 108.
Power input
120 VAC, 60 Hz NEMA 5-
50R
208-240 VAC, 60 Hz
NEMA L14-30R
2
) media gateway
Figure 26, Typical media
December 2003
2
),
2
)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

G650

Table of Contents