System Warning Messages - Toshiba 4300 series Installation And Operation Manual

4300 series three phase 30/50 kva ups
Table of Contents

Advertisement

PHIRER
Input phase rotation error.
UPSOL
UPS Overload.
VOOV
Output Overvoltage – Output over-
voltage condition occurred.
VOUV
Output Undervoltage – Output
undervoltage condition occurred.
12.21

System Warning Messages

Warning messages are generated when a noncritical abnormal operating condition occurs. The following
tables shows possible messages and their meaning.
When a Warning condition exists, the amber LED on the UPS display panel will flash for the duration of
the Warning condition.
Display
ASYN
Asynchronous mode – Input and
output frequency are different.
Bypass is disabled.
BLFEND
Battery Lifetime End – Batteries
at end of life.
BLFNE
Battery Lifetime Near End – Bat-
teries are nearing the end of their
expected lifetime.
BMCCBO
Battery MCCB is OFF - Backup
power is not available.
BOH
Battery Overheat – Battery not
within specifications.
BTFAIL
Battery Test Failed – Battery not
within specifications.
BYP
UPS is in bypass mode.
CALL
Service Call Required – Inspec-
tion of the unit is advised.
COV
Charger Overvoltage – Battery
Charger not within specifications.
CL
Current Limit – UPS not within
specifications.
EEUPDER EEPROM Update error.
58
Input phase rotation is reversed. Switch any two input
cable connections: A and B, B and C, or C and A.
Reduce equipment load to 100% or less.
UPS is possibly faulty. Check the UPS operation
conditions at time of fault. Not advisable to restart the
UPS. Call for service.
UPS is possibly faulty. Check the UPS operation
conditions at time of fault. Not advisable to restart the
UPS. Call for service.
TABLE 12.6 - SYSTEM WARNING MESSAGES
Meaning
No Action Needed.
Have batteries replaced immediately.
Contact the nearest Toshiba authorized representa-
tive to arrange for battery replacement.
Switch Battery Breaker ON.
Contact the nearest Toshiba authorized representa-
tive for service.
Contact the nearest Toshiba authorized representa-
tive for service.
Switch UPS On-Line.
Have inspection/service performed.
Contact the nearest Toshiba authorized representa-
tive for service.
Contact the nearest Toshiba authorized representa-
tive for service.
Contact the nearest Toshiba authorized representa-
tive for service.