Operating The Ups; Ac Input Mode (Normal Operation); Bypass Mode - Toshiba 4200FA User Manual

Uninterruptible power system three-phase 15/ 25/ 30/ 33/ 50 kva ups
Hide thumbs Also See for 4200FA:
Table of Contents

Advertisement

Operating the UPS

5.7
Operating the UPS
5.7.1

AC Input Mode (Normal Operation)

The following illustration shows circuit power flow when the UPS is operating normally in the
AC Input Mode. The rectifier includes a boost chopper circuit that converts the AC input power
into DC power. The boost chopper circuit maintains a constant voltage with current limiting
abilities for charging the batteries. The rectifier supplies a DC voltage of the proper level to the
inverter section. The inverter section generates a high quality sine wave output voltage. The
batteries are maintained in a constantly charged state when the UPS is in the "Normal
Operation Mode."
Isolation
Transformer
Model
Input
Power
5.7.2

Bypass Mode

If the UPS unit is severely overloaded or develops an internal fault, power flow is automatically
switched from the main circuit to the Bypass circuit. Power flow through the bypass is shown
in the following illustration. This changeover occurs automatically in less than 4 milliseconds in
phase (Make-Before-Break). If the power flow is transferred to the Bypass circuit because of
an overload and that overload condition ends within a specified period of time, then the power
flow will "re-transfer" to the AC Input Mode (Normal Operation) automatically. If the power
flow is transferred to the Bypass circuit due to a fault condition, then the power flow
must be transferred manually from the UPS's Bypass circuit back to the Inverter circuit
after repairing the fault (see "Start-up Procedure"). If the power flow is transferred to the
Bypass circuit due to an overload condition, then the power flow will automatically
transfer from the UPS's Bypass circuit back to the Inverter circuit after removing the
overload (see "Overload Operation").
Isolation
Transformer
Model
Input
Power
5.7.2.1 Bypass Mode for Optional Alternate Input Models
TOSHIBA
MBS
Bypass
Converter
MCCB
Power flow in AC Input Mode
MBS
Bypass
Converter
MCCB
Power flow in Bypass mode
36
Inverter
Chopper
Batteries
Inverter
Chopper
Batteries
Output
Power
Output
Power

Advertisement

Table of Contents
loading

Table of Contents