Trane IntelliPak Signature Series Programming Manual page 60

Commercial self-contained signature series, 20-80 ton modular series, 20-35 ton, “ao” and later design sequence
Hide thumbs Also See for IntelliPak Signature Series:
Table of Contents

Advertisement

60
Programming
(On units with a VCM installed and preheat enabled)
Preheat Output ON If Preheat Temp Below
Preheat Activation Temperature:
Factory Presets: 35 F
Possible Values:
1. Pressing the NEXT key will display the following screen.
(On units with IGV or VFD. Also, on units with SAT control without air
volume control and supply air pressure sensor installed)
Default Supply Air Pressure:
High Limit:
4.0 IWC
Factory Presets: Setpoint = 1.5 IWC
Possible Values:
Note: The high limit setpoint cannot be adjusted below the parameters of the following
equation: The high limit = Deadband - 0.1
1. Pressing the NEXT key will display the following screen.
Low Ambient Comp Lockout Temp:
Comp (s) OFF If OA Temp Below This Value
Factory Presets: 50 F
Possible Values:
1. Pressing the NEXT key will display the following screen.
Setpoint Source Selections Submenu
Press ENTER to Review or Adjust
1. Pressing the NEXT key will display the following screen.
For Supply Air Temp Cooling Control, Use
Setpoint From: HI (KEYPAD) SETPOINT MENU
Factory Presets: HI (Keypad) Setpoint Menu
Possible Values:
1. Pressing the NEXT key will display the following screen.
SETPOINT
35 F
35-75 F
1.5 IWC
Deadband:
0.5 IWC
High Limit = 4.0 IWC
Deadband = 0.5 IWC
Setpoint = 1.0-4.3 IWC
High Limit = 1.2-4.7 IWC
Deadband = 0.1-2.0 IWC
-20-80 F
HI (Keypad) Setpoint Menu
Zone Sensor Setpoint Menu
NSB Zone Sensor Setpoint Input
GBAS 0-5 VDC Module
2
50 F
PKG-SVP01B-EN