Trane IntelliPak Signature Series Programming Manual page 58

Commercial self-contained signature series, 20-80 ton modular series, 20-35 ton, “ao” and later design sequence
Hide thumbs Also See for IntelliPak Signature Series:
Table of Contents

Advertisement

58
Programming
(On units with hydronic, electric, or external heat only)
Default Occupied Zone Setpoint(s)
Cool:
74 F
Factory Presets: Heat = 71 F
Possible Values:
Note: A minimum difference of 2 F is maintained between heating and cooling setpoints.
1. Pressing the NEXT key will display the following screen.
(On units with hydronic heat only)
When Economizer Cooling, Reduce Zone
Temperature Cooling Setpoint By:
Factory Presets: 1.5 F
Possible Values:
1. Pressing the NEXT key will display the following screen.
(On cooling-only units)
Default Unoccupied Zone Temp Setpoint(s)
Cool:
85 F
Factory Presets: 85 F
Possible Values:
1. Pressing the NEXT key will display the following screen.
(On units with hydronic, electric, or external heat only)
Default Unoccupied Zone Temp Setpoint(s)
Cool: 85 F
Heat: 60 F
Factory Presets: Cool = 85 F
Possible Values:
Note: A minimum difference of 2 F is maintained between heating and cooling setpoints.
Also, the morning warmup cannot be lower than the heating setpoint.
1. Pressing the NEXT key will display the following screen.
SETPOINT
Heat:
71 F
Cool = 74 F
Heat = 50-90 F
Cool = 52-92 F
0.0-3.0 F
50-90 F
Morn Warmup: 72 F
Heat = 60 F
MWU = 72 F
Cool = 52-90 F
Heat = 50-88 F
MWU = 50-90 F
1.5 F
PKG-SVP01B-EN