SETUP Menu

The setup menu allows the user to input
unit control parameters; i.e., setpoint
source selection, sensor source selec-
tions, ventilation override definitions,
functions enable/disable, status, text
display (language), temperature display
(C or F), and system tuning parameters.
When a setup screen displays for 30
minutes without a key being pressed, the
LCD screen will revert to the appropriate
power-up display. If this happens, press
the SETUP key again to return to the
setup menu.
Note: Some of the screens in this section
may not be visible on your HI since they
are applicable only for specific unit options.
Press the SETUP key to begin viewing or
modifying the SETUP screens. Follow this
procedure when viewing a screen that
requires modification:
1. Press the + or - key until the proper
value displays.
2. Press the ENTER key to confirm your
choice.
3. Press the NEXT key to advance the
cursor.
4. Repeat steps 1 and 2 if there are
additional values on the same screen
that require changing.
32
Programming
SETUP Menu Screens
Press the SETUP key to display the following screen(s).
Display Text in:
Display Units Using:
Factory Presets: Text and Units = English
Possible Values:
1. Pressing the NEXT key will display the following screen.
(On units with a TCI module)
Unit Control:
Unit Address:
Factory Presets: Control = Local
Possible Values:
1. Pressing the NEXT key will display the following screen.
General Unit Functions Setup Submenu
Press ENTER to Review or Adjust
1. Pressing the NEXT key will display the following screen.
(On units with VFD and bypass)
Supply Fan VFD Mode:
Factory Presets: Mode = Normal
Possible Values:
1. Pressing the NEXT key will display the following screen.
If Remote Panel Mode Input Not Present:
System Mode: AUTO
Possible Values:
1. Pressing the NEXT key will display the following screen.
Daytime Warmup Function:
Factory Preset:
Possible Values:
1.Pressing the NEXT key will display the following screen.
SETUP
ENGLISH LANGUAGE
ENGLISH NOTATION
Text = English, French, Spanish
Units = English, SI
LOCAL
31
Address = 1
Unit Control = Local, ICS (Tracer Summit
Unit Address = 0-31
BYPASS
Address = 1
Mode = Normal, Bypass
System Mode = Off, Auto
DISABLED
Disabled
Daytime Warmup Function = Enabled, Disabled
®
)
PKG-SVP01B-EN