Trane IntelliPak Signature Series Programming Manual page 39

Commercial self-contained signature series, 20-80 ton modular series, 20-35 ton, “ao” and later design sequence
Hide thumbs Also See for IntelliPak Signature Series:
Table of Contents

Advertisement

PKG-SVP01B-EN
Programming
(On units with waterside economizer)
Water Economizer Min Position:
Possible Values:
0-100%
1. Pressing the NEXT key will display the following screen.
(On water-cooled units with waterside economizer)
Select Water Flow Control Required For
Water Pump System:
Possible Values:
Constant/Maximize
Variable/Minimize
1. Pressing the NEXT key will display the following screen.
End of Submenu (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
Head Pressure Ctrl Setup Submenu
Press ENTER to Review or Adjust
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units)
Cond Temp Control Point:
Possible Values:
80-100 F
1. Pressing the NEXT key will display the following screen.
(On all water-cooled units)
Preset Value to Min if Cond Water Below
Head Press Value Preset Temp Limit:
Possible Values:
0-99 F
1. Pressing the NEXT key will display the following screen.
(On all air-cooled units)
Cond Temp Control Band
Lower Limit:
80 F
Factory Presets: Lower = 80 F
Upper = 120 F
Possible Values:
Lower = 70-90 F
Upper = 110-130 F
1. Pressing the NEXT key will display the following screen.
SETUP
10 %
Variable/Minimize
90 F
90 F
Upper Limit:
120 F
39

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Intellipak signature scwg-020Intellipak signature scwg-025Intellipak signature scwg-030Intellipak signature scwg-035Intellipak signature siwg-020Intellipak signature siwg-025 ... Show all

Table of Contents