PKG-SVP01B-EN
Programming
(On air-cooled units, 40-60 Tons)
Condenser Fan Outputs
1A
OFF
1B OFF
Factory Presets: Off
Possible Values:
On, Off, Auto
1. Press the NEXT key to advance the cursor to the next field within this screen.
2. Press the NEXT key again to display the following screen.
(On air-cooled units)
Condenser Fan Speed
Ckt 1
0%
Factory Presets: 0%
Possible Values:
0-100%, Auto
1. Press the NEXT key again to display the following screen.
(On air-cooled units)
Condenser Fan Speed
Ckt 1
0%
Factory Presets: 0%
Possible Values:
0-100%, Auto
1. Press the NEXT key to advance the cursor to the next field within this screen.
2. Press the NEXT key again to display the following screen.
Compressor Relays:
K11 OFF
K3 OFF
Factory Presets: Off
Possible Values:
On, Off
1. Press the NEXT key to advance the cursor to the next field within this screen.
2. Press the NEXT key again to display the following screen.
(On units with hydronic heat)
Hydronic Heat
Actuator
0 %
Factory Presets: 0%
Possible Values:
0-100%, Auto
1. Press the NEXT key again to display the following screen.
SERVICE MODE
2A OFF
2B OFF
Ckt 2
0%
K12 OFF
K4 OFF
69