Trane IntelliPak Signature Series Programming Manual page 47

Commercial self-contained signature series, 20-80 ton modular series, 20-35 ton, “ao” and later design sequence
Hide thumbs Also See for IntelliPak Signature Series:
Table of Contents

Advertisement

PKG-SVP01B-EN
Programming
End of Submenu (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
RTM Alarm Output Diagnostic Assignment Screens
RTM Alarm Output Diagnostic Assignments
Press ENTER to Review or Adjust
1. Pressing the NEXT key will display the following screen.
Assign Diagnostic to RTM Alarm Output ?
Any Active Diagnostic
Factory Presets: Any Active Diagnostic
Possible Values:
Refer to the list of active diagnostics that can be assigned
to each GBAS output definition in the "Diagnostic Menu"
section on page 72.
1. Press the ENTER key, then the NEXT key to display the possible diagnostics that may
be assigned to the RTM alarm output definition.
2. Press the + (plus) key to assign "yes" to the output definition or - (minus) key to
assign "no" to the output definition.
3. Press the ENTER key to confirm each selection.
Note: Assigning "yes" to an alarm output definition means that if the assigned diagnostic
is present, the RTM alarm output will energize.
End of Submenu (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
SETUP
(No)
47