Trane IntelliPak Signature Series Programming Manual page 43

Commercial self-contained signature series, 20-80 ton modular series, 20-35 ton, “ao” and later design sequence
Hide thumbs Also See for IntelliPak Signature Series:
Table of Contents

Advertisement

PKG-SVP01B-EN
Programming
(On units with a VCM)
OA Flow CO2 Reset Function:
Possible Values:
Enabled, Disabled
1. Pressing the NEXT key will display the following screen.
(On units with a VCM installed and CO2 reset enabled)
OA Flow CO2 Reset Function:
CO2 Start: 800 PPM
Possible Values:
Enabled, Disabled
CO2 Start = 0-1900 PPM
CO2 Max = 100-2000 PPM
1. Pressing the NEXT key will display the following screen.
(On units with an airside economizer with Traq™ damper)
TRAQ Damper Quantity:
TRAQ Damper Size:
Possible Values:
Quantity = 1-12
Size = 0, 13, 16, 20, 24, or 28
1. Pressing the NEXT key will display the following screen.
(On units with a VCM)
OA Flow Calibration Data:
Gain: 1.0
Factory Presets: Gain = 1.0
Offset = 0.0
Possible Values:
Gain = 0.0-1.5
Offset = -25.0-25.0
1. Pressing the NEXT key will display the following screen.
End of Submenu (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
Ventilation Override Definitions
(On units with a VOM)
Ventilation Override Definitions
Press ENTER to Review or Adjust
1. Pressing the NEXT key will display the following screen.
SETUP
ENABLED
ENABLED
CO2 Max: 1000 PPM
1
28 Inches
Offset:
0.0 CCFM
43