Trane IntelliPak Signature Series Programming Manual page 41

Commercial self-contained signature series, 20-80 ton modular series, 20-35 ton, “ao” and later design sequence
Hide thumbs Also See for IntelliPak Signature Series:
Table of Contents

Advertisement

PKG-SVP01B-EN
Programming
(On all units except those with supply air temperature control without IGV
or VFD)
For Occupied Zone Temp Ctrl, Use Sensor
Connected To:
Possible Values:
RTM Zone Temp Input
NSB Zone Sensor
RTM Aux Temp Input
Heat Module Aux Temp Input
ECEM Return Air Temp Input
1. Pressing the NEXT key will display the following screen.
For Unoccupied Zone Temp Ctrl, Use Sensor
Connected To:
Possible Values:
RTM Zone Temp Input
NSB Zone Sensor
RTM Aux Temp Input
Heat Module Aux Temp Input
ECEM Return Air Temp Input
1. Pressing the NEXT key will display the following screen.
( On units with electric, hydronic, or external heat only)
For Morning Warmup Temp Ctrl, Use Sensor
Connected To:
Possible Values:
RTM Zone Temp Input
NSB Zone Sensor
RTM Aux Temp Input
Heat Module Aux Temp Input
ECEM Return Air Temp Input
1. Pressing the NEXT key will display the following screen.
For Zone Reset Function, Use Sensor
Connected To:
Possible Values:
RTM Zone Temp Input
NSB Zone Sensor
RTM Aux Temp Input
Heat Module Aux Temp Input
ECEM Return Air Temp Input
1. Pressing the NEXT key will display the following screen.
SETUP
RTM ZONE TEMP INPUT
RTM ZONE TEMP INPUT
RTM ZONE TEMP INPUT
RTM ZONE TEMP INPUT
41